| Date |
Text |
| 2005-06-20 00:00:00 | *********** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE SEE THERE ARE MANY PLACES |
| | LOCATED ON PLANS IN WHICH THE 1999 NEC |
| | IS REFERENCED. PLEASE KNOW, THE STATE OF |
| | FLORIDA ADOPTED 2002 NEC 7/1/03. |
| | PLEASE SEE THERE ARE PLACES WHERE 2000? |
| | NEC IS NOTED. |
| | |
| | 2)NOTE: PLEASE SEE ALTERNATING CIRCUITS |
| | FOR EMERGENCY EGRESS LIGHTING IS |
| | PROVIDED FOR STAIRWELLS, HOWEVER COMMON |
| | AREAS, COMMON AREA CORRIDORS ARE NOT |
| | CIRCUITED THE SAME WAY? |
| | PLEASE SEE LS 101 7-8,7-9 |
| | |
| | 3)NOTE: PLEASE SEE ENTRY LT PROVIDED |
| | FROM UNITS TO COMMON AREA HALLS? |
| | PLEASE SEE 210.25 FOR CIRCUITS NOT |
| | PERMITTED IN COMMON AREAS. PLEASE |
| | UNDERSTAND A MEANS OF EGRESS CONTROL OR |
| | FIXTURE IS NOT REQUIRED UNDER 210.70. |
| | |
| | 4)NOTE: PLEASE CLARIFY/ SHOW GFI WITHIN |
| | 20' OF POOL. 680.22A3 |
| | |
| | 5)NOTE: PLEASE SEE 210.52C1-5 |
| | PLEASE SEE PENINSULARS AND ANY ISLAND |
| | AREAS WHERE SEPARATED BY A SINK, STOVE |
| | ETC, REQUIRED AN ADDITIONAL RECEPT. |
| | PLEASE SEE SOME AREAS CIRCLED ON PLANS. |
| | C-1, A-1, B-1 ETC. |
| | |
| | 6)NOTE: PLEASE SEE WRONG CODE ART. |
| | REFERENCED FOR GFI PROTECTION OF KITCHEN |
| | COUNTERSPACES. PLEASE SEE 210.8A6 |
| | NOTE #15 ON UNIT SHEETS. |
| | |
| | 7)NOTE: PLEASE SEE MISSING CONTROL FOR |
| | LT UNI9T G-3 |
| | |
| | 8)NOTE: PLEASE SEE MANY UNITS ARE SHOWN |
| | AS "LOFT UNITS", HOWEVER NO STAIRS |
| | SHOWN, NO LOFT AREA SHOWN OR SUBMITTED. |
| | PLEASE SEE ONLY SOME UNITS ALSO SHOW |
| | LOFT AREAS. |
| | 215.5 |
| | |
| | 9)NOTE: PLEASE SEE MISSING RECEPTS PER |
| | 210.52. PLEASE SEE 2',6',12' RULE. |
| | PLEASE SEE WALL AREAS BY STAIRS, LOFT |
| | AREA, RAILS ARE ALSO CONSIDERED TO BE |
| | WALL SPACE. |
| | PLEASE SEE ONE C-1 UNIT SHOW RECEPT IN |
| | "AIRSPACE" FROM LOFT AREA. |
| | |
| | 10)NOTE: PLEASE SEE MISSING GFI W/IN 3' |
| | OF SINKS. 210.52D. PLEASE SEE IT IS NOT |
| | PERMITTED TO CROSS OVER SINK/LAV AREA TO |
| | SERVE OTHER SIDE. |
| | |
| | 11)NOTE: PLEASE SEE ARC FAULT PROTECTION |
| | NOTED TO THE 1999 NEC. PLEASE ADJUST TO |
| | 2002. |
| | |
| | 12)NOTE: PLEASE SEE UNITS INDICATE |
| | "J-BOX" FOR ALL AREAS? PLEASE SEE |
| | 210.70, LS101, A EGRESS LT FIXTURE OF |
| | SOME KIND SHALL BE INDICATED AND SHOWN |
| | FOR MIN EGRESS LIGHTING. |
| | |
| | 13)NOTE: PLEASE CLARIFY #'S SHOWN IN |
| | BATH AREAS? #19, #20, #23 ETC? |
| | |
| | 14)NOTE: PLEASE INCLUDE NOTE ON PLANS |
| | FOR FHAR ,24CFR 100.205. IT IS NOTED |
| | FOR CORRECT HEIGHTS. |
| | |
| | 15)NOTE: PLEASE INCLUDE NOTE ON PLANS |
| | FOR METER ELECTRICAL RMS TO MEET 110.26. |
| | PLEASE PLACE THIS NOTE ON ROOM LAYOUT |
| | SHEET. E4.0 |
| | |
| | 16)NOTE: PLEASE SEE POSSIBLE MECHANICAL |
| | REVIEW NOTES PERTAINING TO BOOSTER FANS. |
| | THIS IS ONLY A "HEADS-UP NOTE FOR |
| | POSSIBLE MECH ISSUES. |
| | |
| | 17)NOTE: PLEASE LABEL ALL MAINS ON RISER |
| | DIAGRAM. PLEASE SEE SIGNAGE SHOULD BE |
| | NOTED AND SHALL BE INSTALLED WITH A MIN |
| | OF 1" LETTERING ON A CONTRASTING BACK |
| | GROUND. |
| | |
| | 18)NOTE: PLEASE INCLUDE EQUIPMENT |
| | GROUNDING CONDUCTORS FOR FEEDERS ETC ON |
| | RISER/ FEEDER SCHEDULE. |
| | PLEASE SEE GEN ETC. |
| | |
| | 19)NOTE: PLEASE CLARFIY IF SEC'S TO ATS |
| | ARE LOCATED OVERHEAD OR UNDERGROUND. |
| | PLEASE SEE SEC'S ARE NOT PERMITTED TO BE |
| | OVER 8' WITH OUT OCP INSIDE BLDG. |
| | 230.70 |
| | |
| | 20)NOTE: PLEASE VERIFY PANELS FOR UNITS |
| | SHOWN AS 42 POLES AND 30 POLES. PLEASE |
| | ALSO VERIFY PANELS SHOWN AS 30POLE AS |
| | 225A. ALL PANELS ARE SHOWN AS 225A? |
| | 215.5 |
| | |
| | 21)NOTE: PLEASE SEE ALL UNITS SHOW |
| | FEEDERS AS 1/0'S AND #1'S. PLEASE SEE |
| | EACH UNIT INDICATES 200A OCP ??? |
| | PLEASE SEE SIZING OF FEEDERS PER 310.16 |
| | #1 ONLY RATED FOR 130A'S AND 1/0'S FOR |
| | 150A'S. |
| | |
| | 22)NOTE: PLEASE NOTE: NO ALUM PERMITTED |
| | AS EQUIPMENT GROUNDING. |
| | PLEASE SEE NO ALUM PERMITTED SMALLER |
| | THAN #2. PER LOCAL AMENDMENTS. |
| | 250.62, 310.2 |
| | |
| | 23)NOTE: PLEASE VERIFY FEED TO OAIU? |
| | THIS PANEL?OR "? COULD NOT BE LOCATED ON |
| | RISER OR PANEL SCHEDULE FOR THIS? |
| | 215.5 |
| | |
| | 24)NOTE: PLEASE CLARFIY 230.95/ GFI |
| | PROTECTION FOR MDPE? |
| | |
| | 25)NOTE: PLEASE CLARIFY IS EACH |
| | "SHUNT-TRIP MAINALSO CONTAIN A MANUAL |
| | MEANS OF DISCLOCATED ON THE OUTSIDE OF |
| | EQUIPMENT. 230.76,230.79 |
| | |
| | 26)NOTE: PLEASE SEE RISER, NOTES ETC |
| | DOES NOT INDICATE A BRKR OR OCP SIZE FOR |
| | FP FROM GENERATOR? |
| | 215.5 |
| | |
| | 27)NOTE: PLEASE SUBMIT ALL MANUFACTURE |
| | SPEC/CUT SHEETS FOR FIRE PUMP. PLEASE |
| | SEE PLANS DO NOT SHOW SIZE OF FP, OCP |
| | SET FOR LOCKED ROTOR ETC PER 695.3B1 |
| | PLEASE SEE FIRE PUMP DETAIL MENTIONS A |
| | BRKR AT GEN, HOWEVER NO INFORMATION WAS |
| | SUBMMITTED TO VERIFY. |
| | PLEASE ALSO SUBMIT ALL SPECS ON FIRE |
| | PUMP CONTROLLER. ALL MUST MEET ALL |
| | LISTINGS UNDER A NRTL, NFPA-20, NFPA-110 |
| | NFPA-70. |
| | UNABLE TO VERIFY AT THIS TIME. |
| | |
| | 28)NOTE: PLEASE SUBMIT ALL MANUFACTURE |
| | SPECS FOR GEN/ ATS / SUB-BASE FUEL TANK |
| | SHOWING ALL LISTINGS UNDER A NRTL. |
| | FUEL TANK SPECS SHALL BE REVIEWED BY |
| | FIRE AND MECH REVIEW. |
| | |
| | |
| | 29)NOTE: PLEASE VERIFY BY NOTING ON |
| | PLANS WEATHER OR NOT GEN WILL OR WILL |
| | NOT BE A "SEPARATELY DERIVED" SYSTEM? |
| | PLEASE SEE MDPE IS SHOWN AS GFI? |
| | |
| | |
| | 30)NOTE: PLEASE SEE FEED TO FIRE PUMP |
| | FROM GEN WILL BE REQUIRED TO BE |
| | INSTALLED IN 2" OF CONCRETE OR UNDER |
| | BLDG. PLEASE SEE PLANS ONLY INDICATE A |
| | 1HR RATING? |
| | PLEASE SEE 695.6 A, B, 230.6 |
| | |
| | 31)NOTE:PLEASE SEE RISER DOES NOT |
| | INDICATE OCP FOR FIRE PUMP FROM GEN. |
| | PLEASE ALSO SEE OTHER NOTES.215.5 |
| | |
| | 32)NOTE: PLEASE CORRELATE LOAD CALCS ON |
| | METER CENTER LOAD SUMMARY WITH MAINS. |
| | 215.5 |
| | |
| | 33)NOTE: PLEASE SEE FIRE ALARM RISER |
| | DOES NOT INCLUDE GEN/ FIRE PANEL AS |
| | SHOWN ONLOBBY PLANS. |
| | 215.5 |
| | |
| | 34)NOTE: PLEASE SEE POOL SHALL BE UNDER |
| | A SEPARATE PERMIT. |
| | PLEASE INCLUDE EITHER A NOTE FOR "NO |
| | SWIMMING AFTER DUSK" OR PLEASE INCLUDE |
| | PHOTOMETRIC PLANS WHICH ARE TO BE |
| | SUBMITTED TO THE PALM BEACH COUNTY |
| | HEALTH DEPT FOR REVIEW AND STAMPING |
| | BEFORE RE-SUBMITTING FOR ELECTRICAL |
| | REVIEW. |
| | |
| | 35)NOTE: PLEASE SEE GATES DETAILED ON |
| | 701 WILL BE REQUIRED TO BE UNDER A |
| | SEPARATE PERMIT. PLEASE SEE CONDUITS MAY |
| | BE INSTALLED FOR THESE ONLY. |
| | GATE SPECS WILL BE NEED TO BE SUBMITTED |
| | WHEN SUBMITTING FOR PERMIT. LISTINGS PER |
| | NRTL, FAIL SAFE OPERATION ETC. MIN WIDTH |
| | PER FIRE DEPT. |
| | |
| | 36)NOTE: PLEASE REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO THREE COMPLETE SETS FOR |
| | REVIEW AND STAMPING. ONE SET OF ALL |
| | OLD/VOIDED SHEETS SHALL BE SUBMITTED FOR |
| | REFERENCE. |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY HAVE AN |
| | AFFECT ON ELECTRICAL PLANS. |
| | |
| | PLEASE SEE DUE TO PLANS AND SUBMITTALS |
| | NOT BEING COMPLETE AT THIS TIME, A |
| | COMPLETE REVIEW FOR CODE COMPLIANCECAN |
| | NOT BE DONE FOR ITEMS NOT SUBMITTED. |
| | |
| | PLEASE SEE MANY ITEMS AND LOCATIONS WERE |
| | REDLINED ON PLANS FOR AREAS OF COMMENTS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICALPLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| 2005-06-14 00:00:00 | ONE SET OF ARCH AND MEP IN ELEC FOR |
| | REVIEW. |