2005-06-20 00:00:00*********** UNSAT ***************
  
 1)NOTE: PLEASE SEE THERE ARE MANY PLACES
 LOCATED ON PLANS IN WHICH THE 1999 NEC
 IS REFERENCED. PLEASE KNOW, THE STATE OF
 FLORIDA ADOPTED 2002 NEC 7/1/03.
 PLEASE SEE THERE ARE PLACES WHERE 2000?
 NEC IS NOTED.
  
 2)NOTE: PLEASE SEE ALTERNATING CIRCUITS
 FOR EMERGENCY EGRESS LIGHTING IS
 PROVIDED FOR STAIRWELLS, HOWEVER COMMON
 AREAS, COMMON AREA CORRIDORS ARE NOT
 CIRCUITED THE SAME WAY?
 PLEASE SEE LS 101 7-8,7-9
  
 3)NOTE: PLEASE SEE ENTRY LT PROVIDED
 FROM UNITS TO COMMON AREA HALLS?
 PLEASE SEE 210.25 FOR CIRCUITS NOT
 PERMITTED IN COMMON AREAS. PLEASE
 UNDERSTAND A MEANS OF EGRESS CONTROL OR
 FIXTURE IS NOT REQUIRED UNDER 210.70.
  
 4)NOTE: PLEASE CLARIFY/ SHOW GFI WITHIN
 20' OF POOL. 680.22A3
  
 5)NOTE: PLEASE SEE 210.52C1-5
 PLEASE SEE PENINSULARS AND ANY ISLAND
 AREAS WHERE SEPARATED BY A SINK, STOVE
 ETC, REQUIRED AN ADDITIONAL RECEPT.
 PLEASE SEE SOME AREAS CIRCLED ON PLANS.
 C-1, A-1, B-1 ETC.
  
 6)NOTE: PLEASE SEE WRONG CODE ART.
 REFERENCED FOR GFI PROTECTION OF KITCHEN
 COUNTERSPACES. PLEASE SEE 210.8A6
 NOTE #15 ON UNIT SHEETS.
  
 7)NOTE: PLEASE SEE MISSING CONTROL FOR
 LT UNI9T G-3
  
 8)NOTE: PLEASE SEE MANY UNITS ARE SHOWN
 AS "LOFT UNITS", HOWEVER NO STAIRS
 SHOWN, NO LOFT AREA SHOWN OR SUBMITTED.
 PLEASE SEE ONLY SOME UNITS ALSO SHOW
 LOFT AREAS.
 215.5
  
 9)NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52. PLEASE SEE 2',6',12' RULE.
 PLEASE SEE WALL AREAS BY STAIRS, LOFT
 AREA, RAILS ARE ALSO CONSIDERED TO BE
 WALL SPACE.
 PLEASE SEE ONE C-1 UNIT SHOW RECEPT IN
 "AIRSPACE" FROM LOFT AREA.
  
 10)NOTE: PLEASE SEE MISSING GFI W/IN 3'
 OF SINKS. 210.52D. PLEASE SEE IT IS NOT
 PERMITTED TO CROSS OVER SINK/LAV AREA TO
 SERVE OTHER SIDE.
  
 11)NOTE: PLEASE SEE ARC FAULT PROTECTION
 NOTED TO THE 1999 NEC. PLEASE ADJUST TO
 2002.
  
 12)NOTE: PLEASE SEE UNITS INDICATE
 "J-BOX" FOR ALL AREAS? PLEASE SEE
 210.70, LS101, A EGRESS LT FIXTURE OF
 SOME KIND SHALL BE INDICATED AND SHOWN
 FOR MIN EGRESS LIGHTING.
  
 13)NOTE: PLEASE CLARIFY #'S SHOWN IN
 BATH AREAS? #19, #20, #23 ETC?
  
 14)NOTE: PLEASE INCLUDE NOTE ON PLANS
 FOR FHAR ,24CFR 100.205. IT IS NOTED
 FOR CORRECT HEIGHTS.
  
 15)NOTE: PLEASE INCLUDE NOTE ON PLANS
 FOR METER ELECTRICAL RMS TO MEET 110.26.
 PLEASE PLACE THIS NOTE ON ROOM LAYOUT
 SHEET. E4.0
  
 16)NOTE: PLEASE SEE POSSIBLE MECHANICAL
 REVIEW NOTES PERTAINING TO BOOSTER FANS.
 THIS IS ONLY A "HEADS-UP NOTE FOR
 POSSIBLE MECH ISSUES.
  
 17)NOTE: PLEASE LABEL ALL MAINS ON RISER
 DIAGRAM. PLEASE SEE SIGNAGE SHOULD BE
 NOTED AND SHALL BE INSTALLED WITH A MIN
 OF 1" LETTERING ON A CONTRASTING BACK
 GROUND.
  
 18)NOTE: PLEASE INCLUDE EQUIPMENT
 GROUNDING CONDUCTORS FOR FEEDERS ETC ON
 RISER/ FEEDER SCHEDULE.
 PLEASE SEE GEN ETC.
  
 19)NOTE: PLEASE CLARFIY IF SEC'S TO ATS
 ARE LOCATED OVERHEAD OR UNDERGROUND.
 PLEASE SEE SEC'S ARE NOT PERMITTED TO BE
 OVER 8' WITH OUT OCP INSIDE BLDG.
 230.70
  
 20)NOTE: PLEASE VERIFY PANELS FOR UNITS
 SHOWN AS 42 POLES AND 30 POLES. PLEASE
 ALSO VERIFY PANELS SHOWN AS 30POLE AS
 225A. ALL PANELS ARE SHOWN AS 225A?
 215.5
  
 21)NOTE: PLEASE SEE ALL UNITS SHOW
 FEEDERS AS 1/0'S AND #1'S. PLEASE SEE
 EACH UNIT INDICATES 200A OCP ???
 PLEASE SEE SIZING OF FEEDERS PER 310.16
 #1 ONLY RATED FOR 130A'S AND 1/0'S FOR
 150A'S.
  
 22)NOTE: PLEASE NOTE: NO ALUM PERMITTED
 AS EQUIPMENT GROUNDING.
 PLEASE SEE NO ALUM PERMITTED SMALLER
 THAN #2. PER LOCAL AMENDMENTS.
 250.62, 310.2
  
 23)NOTE: PLEASE VERIFY FEED TO OAIU?
 THIS PANEL?OR "? COULD NOT BE LOCATED ON
 RISER OR PANEL SCHEDULE FOR THIS?
 215.5
  
 24)NOTE: PLEASE CLARFIY 230.95/ GFI
 PROTECTION FOR MDPE?
  
 25)NOTE: PLEASE CLARIFY IS EACH
 "SHUNT-TRIP MAINALSO CONTAIN A MANUAL
 MEANS OF DISCLOCATED ON THE OUTSIDE OF
 EQUIPMENT. 230.76,230.79
  
 26)NOTE: PLEASE SEE RISER, NOTES ETC
 DOES NOT INDICATE A BRKR OR OCP SIZE FOR
 FP FROM GENERATOR?
 215.5
  
 27)NOTE: PLEASE SUBMIT ALL MANUFACTURE
 SPEC/CUT SHEETS FOR FIRE PUMP. PLEASE
 SEE PLANS DO NOT SHOW SIZE OF FP, OCP
 SET FOR LOCKED ROTOR ETC PER 695.3B1
 PLEASE SEE FIRE PUMP DETAIL MENTIONS A
 BRKR AT GEN, HOWEVER NO INFORMATION WAS
 SUBMMITTED TO VERIFY.
 PLEASE ALSO SUBMIT ALL SPECS ON FIRE
 PUMP CONTROLLER. ALL MUST MEET ALL
 LISTINGS UNDER A NRTL, NFPA-20, NFPA-110
 NFPA-70.
 UNABLE TO VERIFY AT THIS TIME.
  
 28)NOTE: PLEASE SUBMIT ALL MANUFACTURE
 SPECS FOR GEN/ ATS / SUB-BASE FUEL TANK
 SHOWING ALL LISTINGS UNDER A NRTL.
 FUEL TANK SPECS SHALL BE REVIEWED BY
 FIRE AND MECH REVIEW.
  
  
 29)NOTE: PLEASE VERIFY BY NOTING ON
 PLANS WEATHER OR NOT GEN WILL OR WILL
 NOT BE A "SEPARATELY DERIVED" SYSTEM?
 PLEASE SEE MDPE IS SHOWN AS GFI?
  
  
 30)NOTE: PLEASE SEE FEED TO FIRE PUMP
 FROM GEN WILL BE REQUIRED TO BE
 INSTALLED IN 2" OF CONCRETE OR UNDER
 BLDG. PLEASE SEE PLANS ONLY INDICATE A
 1HR RATING?
 PLEASE SEE 695.6 A, B, 230.6
  
 31)NOTE:PLEASE SEE RISER DOES NOT
 INDICATE OCP FOR FIRE PUMP FROM GEN.
 PLEASE ALSO SEE OTHER NOTES.215.5
  
 32)NOTE: PLEASE CORRELATE LOAD CALCS ON
 METER CENTER LOAD SUMMARY WITH MAINS.
 215.5
  
 33)NOTE: PLEASE SEE FIRE ALARM RISER
 DOES NOT INCLUDE GEN/ FIRE PANEL AS
 SHOWN ONLOBBY PLANS.
 215.5
  
 34)NOTE: PLEASE SEE POOL SHALL BE UNDER
 A SEPARATE PERMIT.
 PLEASE INCLUDE EITHER A NOTE FOR "NO
 SWIMMING AFTER DUSK" OR PLEASE INCLUDE
 PHOTOMETRIC PLANS WHICH ARE TO BE
 SUBMITTED TO THE PALM BEACH COUNTY
 HEALTH DEPT FOR REVIEW AND STAMPING
 BEFORE RE-SUBMITTING FOR ELECTRICAL
 REVIEW.
  
 35)NOTE: PLEASE SEE GATES DETAILED ON
 701 WILL BE REQUIRED TO BE UNDER A
 SEPARATE PERMIT. PLEASE SEE CONDUITS MAY
 BE INSTALLED FOR THESE ONLY.
 GATE SPECS WILL BE NEED TO BE SUBMITTED
 WHEN SUBMITTING FOR PERMIT. LISTINGS PER
 NRTL, FAIL SAFE OPERATION ETC. MIN WIDTH
 PER FIRE DEPT.
  
 36)NOTE: PLEASE REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO THREE COMPLETE SETS FOR
 REVIEW AND STAMPING. ONE SET OF ALL
 OLD/VOIDED SHEETS SHALL BE SUBMITTED FOR
 REFERENCE.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 PLEASE SEE DUE TO PLANS AND SUBMITTALS
 NOT BEING COMPLETE AT THIS TIME, A
 COMPLETE REVIEW FOR CODE COMPLIANCECAN
 NOT BE DONE FOR ITEMS NOT SUBMITTED.
  
 PLEASE SEE MANY ITEMS AND LOCATIONS WERE
 REDLINED ON PLANS FOR AREAS OF COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICALPLAN REVIEW
 561-805-6717
 [email protected]
  