| Plan Review Notes For Permit 05050621 |
| Permit Number |
05050621 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-06-23 00:00:00 | | | | | | | PROVISO | | | ~~~~~~~ | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | ALONG WITH ANY REVISIONS, PRIOR TO ROUGH | | | INSPECTION. | | | | | | 1} THE GROUNDING ELECTRODE CONDUCTOR | | | MUST BE A MINIMUM OF #1/0 CU TO COMPLY | | | WITH 250.66. THIS IS CRITICAL AT THE | | | BEGINING STAGES OF THE JOB AS IT | | | CONNECTS TO FOOTER STEEL. | | | | | | 2} INDICATE THE SIZE OF THE GUTTER SHOWN | | | ON THE RISER PER 366.6. ALSO SHOW | | | DISCONNECT LOCATIONS ON THE DRAWING. | | | | | | 3 THE 2" CONDUIT TO FPL IS TOO SMALL FOR | | | THE CONDUCTORS LISTED. SEE TABLES. C-10 | | | IF PVC. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|