| Plan Review Notes For Permit 05050621 |
| Permit Number |
05050621 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-05-27 00:00:00 | | | | | | | | | | | | | 1} PLEASE SUBMIT PANEL SCHEDULES WITH | | | CIRCUIT DESIGNATIONS,OCP AND WIRE SIZE | | | TO BRANCH CIRCUITS. | | | | | | 2} THE 3-"MAIN BREAKER" 200AMP | | | DISCONNECTS AS STATED ON THE RISER WOULD | | | BE IN VIOLATION OF 310.15(B) FEEDING #1 | | | CONDUCTORS TO THE PANELS. PLEASE | | | CLARIFY. | | | | | | 3}INDICATE THE SIZE OF THE GROUNDING | | | ELECTRODE CONDUCTOE PER 250.66. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|