| Plan Review Notes For Permit 05050580 |
| Permit Number |
05050580 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-05-28 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. SHT 1 SANITARY RISER DIAGRAMS. | | | CORRECT THE FOLLOWING: | | | A. BIDET IS NOT VENTED. SECTION 901.2.1 | | | B. CLEANOUT REQUIRED 4' ABOVE THE FLOOR | | | SECTION 708.10 | | | C. SHOW ALL PIPE SIZES. TABLE 710.1(1) | | | 2. ALL SHEETS ARCHITECT LICENSE NUMBER | | | IS REQUIRED IN TITLE BLOCK. | | | 61G1-16.004(2) AND FS 481.2055 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|