2005-11-28 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05050549
 ADD: 911 PASEO ANDORRA
 CONT: O/B ORDONEZ, SANTANDER
 TEL: (561)655-6119
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1)UNDER THE FIRST PLAN REVIEW THERE WAS
 AN ENGINEER TAKING RESPONSIBILITY FOR
 THE DRAWINGS, THE CURRENT PLANS DO NOT
 INDICATE THAT THEY WERE DRAWN BY A
 DESIGN PROFESSIONAL BUT WHOEVER TAKING
 RESPONSIBILITY FOR THE PLANS AND DESIGN
 STILL NEED TO BEAR THE NAME AND
 SIGNATURE OF THAT PARTY.FBC 104.2.1
 ALL INFORMATION, DRAWINGS,SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.PLEASE
 COMPLY.
  
 2)THE SUBMITTED PHOTOGRAPHS SUBMITTED OF
 WATER DAMAGE IS A DIRECT RESULT OF
 IMPROPER BUILDING TECHNIQUES.THE
 SHEATHING APPEARS TO BE BURIED RIGHT
 INTO THE CONCRETE AND WITHIN 2-3"OF THE
 PATIO ON THE OTHER WALL.
 2304.2.5 CLEARANCE BETWEEN WOOD SIDING
 AND EARTH ON THE EXTERIOR OF A
 BUILDING SHALL BE NOT LESS THAN 6 INCHES
 (152 MM) EXCEPT WHERE SIDING,SHEATHING
 AND WALL FRAMING ARE OF APPROVED
 PRESERVATIVE-TREATED WOOD OR
 APPROVED NATURALLY DURABLE WOOD.
 INDICATE HOW THIS WILL BE CORRECTED.
  
 3) THE FOOTING SIZE IS NOT CODE
 COMPLIANT BECAUSE OF (3) CODE ARTICLES,
 3A) 1804.1.3 THE BOTTOM OF FOUNDATIONS
 SHALL EXTEND NO LESS THAN 12 INCHES
 (305 MM) BELOW FINISH GRADE.
 3B)1403.1.6 IN ORDER TO PROVIDE FOR
 INSPECTION FOR TERMITE INFESTATION,
 CLEARANCE BETWEEN EXTERIOR WALL
 COVERINGS AND FINAL EARTH GRADE ON THE
 EXTERIOR OF A BUILDING SHALL NOT BE LESS
 THAN 6 INCHES (152 MM).
 3C) 2304.2.5 CLEARANCE BETWEEN WOOD
 SIDING AND EARTH ON THE EXTERIOR OF A
 BUILDING SHALL BE NOT LESS THAN 6 INCHES
 (152 MM) EXCEPT WHERE SIDING,
 SHEATHING AND WALL FRAMING ARE OF
 APPROVED PRESERVATIVE-TREATED WOOD OR
 APPROVED NATURALLY DURABLE WOOD.
 WITH THE 12" OF FOUNDATION IN THE
 GROUND THE CODE STILL REQUIRES AN
 ADDITIONAL 6" IN HEIGHT AS REQUIRED
 2304.2.5/ 1403.1.6. THIS STILL DOES NOT
 PROVIDE ANY LAP OF THE SHEATHING OR
 STUCCO. THE MINIMUM HEIGHT OF THE
 FOUNDATION SHOULD BE 19" WHICH WILL
 PROVIDE A 1" COVER OR CREATE A STEPED
 WALL ALLOWING THE GRADE TO BE A LITTLE
 HIGHER. 1804.1.7* FINISH GRADE SHALL BE
 SLOPED AWAY FROM THE FOUNDATION FOR
 DRAINAGE. THE LOWEST BUILDING FLOOR
 ELEVATION AT THE PERIMETER OF A
 MONOLITHIC FOUNDATION AT HABITABLE AREAS
 SHALL BE A MINMUM OF 4 " ABOVE THE
 FINISH GRADE, AT THE BUILDING PERIMETER.
 THE 4" MINIMUM IS FOR IF CBS
 CONSTRUCTION IS USED, WOOD FRAME WITH
 STUCCO VENEER WILL REQUIREA 6"
 CLEARENCE FROM GRADE AS INDICATED ABOVE.
  
 4) PLANS INDICATE TO THE FL BLDG CODE
 BUT NOT WHICH EDITION?
  
 5) PLANS INDICATE A CHOICE OF, OR IN LEU
 OF, THE CODE REQUIRES SPECIFIC
 INFORMATION, MANUFACTURER, MODEL TYPE
 ETC AND ALLOWABLE LOADS. THE OTHER ISSUE
 IS WHEREWE GIVE A CERTAIN CODE SECTION
 FOR THE DESIGNER TO FOLLOW, THE DESIGNER
 RESTATES THE CODE SECTION AND NOT
 PROVIDING THE BUILDER (OWNER BUILDER)
 WITH THE REQUIRED INFORMATION. SEE:
 104.2.1* W.P.B. ADMINISTRATIVE
 CODE DRAWINGS & SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF
 NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES.
 SUCH INFORMATION SHALL BE SPECIFIC
 AND THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE
 TERM "LEGAL" OR ITS RQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION".
 5A) 1/2" X 7"FASTENAL STUD PN# 52210
 PROVIDE THE MANUFACTURERS NAME, WILL
 THERE REQUIRE A DERATING SINCE THE STUD
 WOULD BE LESS THAN 2" FROM THE EDGE OF
 CONCRETE? PROVIDE ALLOWABLE UPLIFT WITH
 THE DERATING FACTOR.
 5B) JOIST HANGER DETAIL DOESN'T INDICATE
 IF THIS IS TO TIE INTO THE EXISTING BEAM
 OR IF THE LEDGER WILL BE LOWER THAN THE
 EXISTING BEAM AND WILL TRUELY BOLT
 THROUGH THE BEAM, SPACING OF THE 1/2"
 BOLTS ARE NOT PROVIDED. MISSING THE
 HEIGHT FLOOR TO CEILING 1203.2.1 FOR
 HABITABLE ROOMS 7'-6" IS A MINIMUM.
  
 6)A) PLANS DO NOT INDICATE THE TYPE OF
 ATTACHMENT FOR THE RAFTERS TO THE
 EXISTING BUILDING 104.2.1* ADDITIONAL
 INFORMATION REQUIRED.
 6B) PLANS INDICATE THE USE OF A SIMPSON
 H-5 CLIP TO TIE DOWN THE RAFTERS TO THE
 TOP PLATE BUT NO STRAPS ON TOP OR BOTTOM
 PLATE, PROVIDE A CONTINIOUS LOAD PATH.
 SEE 1606.1.3.
 6C) PLANS SHOW THE INSULATION AT THE
 CEILING LINE THAT BLOCKS OFF AIR FLOW,
 INDICATE COMPLIANCE HOW AIR FLOW WILL BE
 MAINTAINED?
 6D) PLANS INDICATE USE OF 3/8" SHEET
 ROCK ON THE CEILING, PLEASE INDICATE
 WHAT TYPE OF FINISH IS TO BE APPLIED?
 NOTE GYPSUM ASSOC 216 APPLICATION OF
 GYPSUM PANEL PRODUCT TABLE 1 MAXIMUM
 FRAMING SPACING FOR SINGLE LAAYER
 PANEL PRODUCTS INDICATES 3/8"
 PERPENDICULAR, FOOTNOTE "B", ON CEILINGS
 TO RECEEIVE HAND OR SPRAYED APPLYED
 WATER-BASED TEXTURE MATERIALS 1/2"
 GYPSUM CEILING BOARD SHALL BE APPLIED.
 6E) PROVIDE DETAIL ON TIE INTO THE
 EXISTING BUILDING?
 6F) PROVIDE PRODUCT APPROVAL FOR
 DURRAOCK AND USE IN THIS TYPE OF
 APPLICATION, IF THERE IS BLOCKING
 REQUIREMENTS FOR SHEER WALL APPLICATION?
 6G) PROVIDE DETAIL OF NEW ADDITION SLAB
 TIE INTO EXISTING BUILDING?
  
 7) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 8)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A)WINDOWS
 B) TRUSS STRAPS AND BUCKETS
 C) STORM SHUUTTERS ( DOOR WILL ALSO
 REQUIRE STORM SHUTTERS
  
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  