| 2005-11-28 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05050549 |
| | ADD: 911 PASEO ANDORRA |
| | CONT: O/B ORDONEZ, SANTANDER |
| | TEL: (561)655-6119 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 1)UNDER THE FIRST PLAN REVIEW THERE WAS |
| | AN ENGINEER TAKING RESPONSIBILITY FOR |
| | THE DRAWINGS, THE CURRENT PLANS DO NOT |
| | INDICATE THAT THEY WERE DRAWN BY A |
| | DESIGN PROFESSIONAL BUT WHOEVER TAKING |
| | RESPONSIBILITY FOR THE PLANS AND DESIGN |
| | STILL NEED TO BEAR THE NAME AND |
| | SIGNATURE OF THAT PARTY.FBC 104.2.1 |
| | ALL INFORMATION, DRAWINGS,SPECIFICATIONS |
| | AND ACCOMPANYING DATA SHALL BEAR THE |
| | NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN.PLEASE |
| | COMPLY. |
| | |
| | 2)THE SUBMITTED PHOTOGRAPHS SUBMITTED OF |
| | WATER DAMAGE IS A DIRECT RESULT OF |
| | IMPROPER BUILDING TECHNIQUES.THE |
| | SHEATHING APPEARS TO BE BURIED RIGHT |
| | INTO THE CONCRETE AND WITHIN 2-3"OF THE |
| | PATIO ON THE OTHER WALL. |
| | 2304.2.5 CLEARANCE BETWEEN WOOD SIDING |
| | AND EARTH ON THE EXTERIOR OF A |
| | BUILDING SHALL BE NOT LESS THAN 6 INCHES |
| | (152 MM) EXCEPT WHERE SIDING,SHEATHING |
| | AND WALL FRAMING ARE OF APPROVED |
| | PRESERVATIVE-TREATED WOOD OR |
| | APPROVED NATURALLY DURABLE WOOD. |
| | INDICATE HOW THIS WILL BE CORRECTED. |
| | |
| | 3) THE FOOTING SIZE IS NOT CODE |
| | COMPLIANT BECAUSE OF (3) CODE ARTICLES, |
| | 3A) 1804.1.3 THE BOTTOM OF FOUNDATIONS |
| | SHALL EXTEND NO LESS THAN 12 INCHES |
| | (305 MM) BELOW FINISH GRADE. |
| | 3B)1403.1.6 IN ORDER TO PROVIDE FOR |
| | INSPECTION FOR TERMITE INFESTATION, |
| | CLEARANCE BETWEEN EXTERIOR WALL |
| | COVERINGS AND FINAL EARTH GRADE ON THE |
| | EXTERIOR OF A BUILDING SHALL NOT BE LESS |
| | THAN 6 INCHES (152 MM). |
| | 3C) 2304.2.5 CLEARANCE BETWEEN WOOD |
| | SIDING AND EARTH ON THE EXTERIOR OF A |
| | BUILDING SHALL BE NOT LESS THAN 6 INCHES |
| | (152 MM) EXCEPT WHERE SIDING, |
| | SHEATHING AND WALL FRAMING ARE OF |
| | APPROVED PRESERVATIVE-TREATED WOOD OR |
| | APPROVED NATURALLY DURABLE WOOD. |
| | WITH THE 12" OF FOUNDATION IN THE |
| | GROUND THE CODE STILL REQUIRES AN |
| | ADDITIONAL 6" IN HEIGHT AS REQUIRED |
| | 2304.2.5/ 1403.1.6. THIS STILL DOES NOT |
| | PROVIDE ANY LAP OF THE SHEATHING OR |
| | STUCCO. THE MINIMUM HEIGHT OF THE |
| | FOUNDATION SHOULD BE 19" WHICH WILL |
| | PROVIDE A 1" COVER OR CREATE A STEPED |
| | WALL ALLOWING THE GRADE TO BE A LITTLE |
| | HIGHER. 1804.1.7* FINISH GRADE SHALL BE |
| | SLOPED AWAY FROM THE FOUNDATION FOR |
| | DRAINAGE. THE LOWEST BUILDING FLOOR |
| | ELEVATION AT THE PERIMETER OF A |
| | MONOLITHIC FOUNDATION AT HABITABLE AREAS |
| | SHALL BE A MINMUM OF 4 " ABOVE THE |
| | FINISH GRADE, AT THE BUILDING PERIMETER. |
| | THE 4" MINIMUM IS FOR IF CBS |
| | CONSTRUCTION IS USED, WOOD FRAME WITH |
| | STUCCO VENEER WILL REQUIREA 6" |
| | CLEARENCE FROM GRADE AS INDICATED ABOVE. |
| | |
| | 4) PLANS INDICATE TO THE FL BLDG CODE |
| | BUT NOT WHICH EDITION? |
| | |
| | 5) PLANS INDICATE A CHOICE OF, OR IN LEU |
| | OF, THE CODE REQUIRES SPECIFIC |
| | INFORMATION, MANUFACTURER, MODEL TYPE |
| | ETC AND ALLOWABLE LOADS. THE OTHER ISSUE |
| | IS WHEREWE GIVE A CERTAIN CODE SECTION |
| | FOR THE DESIGNER TO FOLLOW, THE DESIGNER |
| | RESTATES THE CODE SECTION AND NOT |
| | PROVIDING THE BUILDER (OWNER BUILDER) |
| | WITH THE REQUIRED INFORMATION. SEE: |
| | 104.2.1* W.P.B. ADMINISTRATIVE |
| | CODE DRAWINGS & SPECIFICATIONS SHALL |
| | CONTAIN INFORMATION, IN THE FORM OF |
| | NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| | CONFORMITY WITH THE TECHNICAL CODES. |
| | SUCH INFORMATION SHALL BE SPECIFIC |
| | AND THE TECHNICAL CODES "SHALL NOT BE |
| | CITED AS A WHOLE OR IN PART, NOR THE |
| | TERM "LEGAL" OR ITS RQUIVALENT BE USED |
| | AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION". |
| | 5A) 1/2" X 7"FASTENAL STUD PN# 52210 |
| | PROVIDE THE MANUFACTURERS NAME, WILL |
| | THERE REQUIRE A DERATING SINCE THE STUD |
| | WOULD BE LESS THAN 2" FROM THE EDGE OF |
| | CONCRETE? PROVIDE ALLOWABLE UPLIFT WITH |
| | THE DERATING FACTOR. |
| | 5B) JOIST HANGER DETAIL DOESN'T INDICATE |
| | IF THIS IS TO TIE INTO THE EXISTING BEAM |
| | OR IF THE LEDGER WILL BE LOWER THAN THE |
| | EXISTING BEAM AND WILL TRUELY BOLT |
| | THROUGH THE BEAM, SPACING OF THE 1/2" |
| | BOLTS ARE NOT PROVIDED. MISSING THE |
| | HEIGHT FLOOR TO CEILING 1203.2.1 FOR |
| | HABITABLE ROOMS 7'-6" IS A MINIMUM. |
| | |
| | 6)A) PLANS DO NOT INDICATE THE TYPE OF |
| | ATTACHMENT FOR THE RAFTERS TO THE |
| | EXISTING BUILDING 104.2.1* ADDITIONAL |
| | INFORMATION REQUIRED. |
| | 6B) PLANS INDICATE THE USE OF A SIMPSON |
| | H-5 CLIP TO TIE DOWN THE RAFTERS TO THE |
| | TOP PLATE BUT NO STRAPS ON TOP OR BOTTOM |
| | PLATE, PROVIDE A CONTINIOUS LOAD PATH. |
| | SEE 1606.1.3. |
| | 6C) PLANS SHOW THE INSULATION AT THE |
| | CEILING LINE THAT BLOCKS OFF AIR FLOW, |
| | INDICATE COMPLIANCE HOW AIR FLOW WILL BE |
| | MAINTAINED? |
| | 6D) PLANS INDICATE USE OF 3/8" SHEET |
| | ROCK ON THE CEILING, PLEASE INDICATE |
| | WHAT TYPE OF FINISH IS TO BE APPLIED? |
| | NOTE GYPSUM ASSOC 216 APPLICATION OF |
| | GYPSUM PANEL PRODUCT TABLE 1 MAXIMUM |
| | FRAMING SPACING FOR SINGLE LAAYER |
| | PANEL PRODUCTS INDICATES 3/8" |
| | PERPENDICULAR, FOOTNOTE "B", ON CEILINGS |
| | TO RECEEIVE HAND OR SPRAYED APPLYED |
| | WATER-BASED TEXTURE MATERIALS 1/2" |
| | GYPSUM CEILING BOARD SHALL BE APPLIED. |
| | 6E) PROVIDE DETAIL ON TIE INTO THE |
| | EXISTING BUILDING? |
| | 6F) PROVIDE PRODUCT APPROVAL FOR |
| | DURRAOCK AND USE IN THIS TYPE OF |
| | APPLICATION, IF THERE IS BLOCKING |
| | REQUIREMENTS FOR SHEER WALL APPLICATION? |
| | 6G) PROVIDE DETAIL OF NEW ADDITION SLAB |
| | TIE INTO EXISTING BUILDING? |
| | |
| | 7) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 8)FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A)WINDOWS |
| | B) TRUSS STRAPS AND BUCKETS |
| | C) STORM SHUUTTERS ( DOOR WILL ALSO |
| | REQUIRE STORM SHUTTERS |
| | |
| | BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |