Plan Review Notes
Plan Review Notes For Permit 05050516
Permit Number 05050516
Review Stop E
Sequence Number 1
Notes
Date Text
2005-05-13 00:00:00 
 PLEASE SUBMIT A RISER DIAGRAM INDICATING
 ELECTRICAL LOCATION OF THE EMERGENCY
 SYSTEM IN CONJUNCTION WITH UTILITY
 SUPPLY.
 THERE IS NO RECORD OF A GENERATOR BEING
 PERMITTED FOR THIS BUILDING.IF THIS IS A
 NEW INSTALLATION PLEASE INCLUDE ALL
 SPECIFICATIONS AND INDICATE PRIME MOVER.
 INCREASE PERMIT VALUE TO INCLUDE ALL
 LABOR AN EQUIPMENT BEING INSTALLED,
 INCLUDING THE TRANSFER SWITCH.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026