| Plan Review Notes For Permit 05050466 |
| Permit Number |
05050466 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-06-13 00:00:00 | DENIED: | | | 1.PLANS ARE TO HAVE A SIGNATURE AND | | | NOT INITIALED OF THE ENGINEER OF RECORD | | | IN ACCORDANCE WITH FS471.025 & FAC | | | 61G15-23.002. | | | | | | 2.PLAN SHEET M5.1 INDICATES AHU | | | SUPPORTED FROM THE BOTTOM OF THE BAR | | | JOIST.PLEASE HAVE THE STRUCTURAL | | | ENGINEER INDICATE IF THIS APPLICATION IS | | | ALLOWED WITH THIS PARTICULAR JOIST/TRUSS | | | SYSTEM. | | | | | | SEE ALSO COMMENT #1 BY DEWEY PALMER, | | | ELECTRICAL PLAN REVIEW. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|