Plan Review Notes
Plan Review Notes For Permit 05050466
Permit Number 05050466
Review Stop E
Sequence Number 1
Notes
Date Text
2005-05-20 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE SEE MISSING LICENSE
 INFORMATION REQUIRED ON TITLE BLOCK FOR
 ARCHITECTUAL FIRM. PLEASE SEE FAC
 61G1-16.004 AND FS 481.219
 THIS IS FOR ARCH FIRM ONLY, NOT FOR ENG
 FIRM.
 PLEASE SEE SOME OF THE ARCHITECTUAL
 SHEETS IN EACH SET ARE NOT SEALED. SEE
 BLDG REVIEW COMMENTS.
 THE ABOVE IS REQUIRED OF ALL TRADES AND
 FOR ALL SHEETS WHEATHER OR NOT COMMENT
 IS MADE BY OTHER REVIEWER(S).
  
 2)NOTE: PLEASE BE SURE ENGINEER OF
 RECORD SIGNS PLANS WITH SIGNATURE ON
 FILE.
 FS 471.025
  
 3)NOTE: PLEASE SEE 450.3 FOR MAX OCP FOR
 TRANSFORMER.
  
 4)NOTE:PLEASE ALSO CORRELATE CONDUCTORS
 FOR FEED TO TRANSFORMERS. SHOWS 1/0 FOR
 GRND?
  
 5)NOTE: PLEASE INDICATE ANY CONTINUOUS
 LAODS AT 125%. 215.3,230.42 ETC.
  
 6)NOTE: PLEASE SEE ANY POSSIBLE COMMENTS
 FROM OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 7)NOTE: PLEASE BE SURE TO REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING ME.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]