2005-06-20 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05050466
 ADD: 4440 BEACON CIR
 CONT: ANDERSON-MOORE
 TEL: (561)753-7400
 *= 2001 FLORIDA BUILDING CODE * WEST
 PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)PROVIDENOC RECORDED WITH THE CLERK OF
 COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) SHEETT INDICATES THIS TO BE A TYPE IV
 UNPROTECTED BUILDING. SHEET 4 DETAIL "A"
 DOES NOT INDICATE THE WALL SUB-SHEATHING
 MATERIAL THAT WILL BE USED?
  
 3)STUCCO VENNER WALLS REQUIRE A TERMITE
 INSPECTION ZONE: 1403.1.6 IN ORDER TO
 PROVIDE FOR INSPECTION FOR TERMITE
 INFESTATION,CLEARANCE BETWEEN
 EXTERIOR WALL COVERINGS AND FINAL EARTH
 GRADE ON THEEXTERIOR OF A BUILDING
 SHALL NOT BE LESS THAN 6 INCHES (152
 MM).
  
 4) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 5) 481.219 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING
 ARCHITECTURAL SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 6) SHEET A-4 PLANS INDICATE THE MAGNET
 WEIGHT TO BE APPROXIMATELY 48,000LBS,
 BUT THE SOILS MINIMUM BEARING CAPACITY
 IS NOT PROVIDED?
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  
  
  
  
  
  
  
  
  