| Plan Review Notes For Permit 05050464 |
| Permit Number |
05050464 |
|
| Review Stop |
P |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2005-11-19 00:00:00 | DENIED; | | | 1. BREAK SINK NOT SHOWN ON SANITARY | | | RISER DIAGRAM. | | | 2.WATER RISER PIPING IS NOT SIZED, SHOCK | | | ARRESTORS FOR BREAK SINK ARE MISSING, | | | WATER SEVICE IS PIPED WRONG AT HEATER | | | AND SHUTOFF VALVE IS NOT SHOWN. | | | 3.WATER RISER DIAGRAM SHOWS HOT AND COLD | | | WATER TO BREAK SINK, AND ALSO HAS A NOTE | | | AT THE SINK CALLING FORINSTA HOT | | | PLEASE CORRECT. | | | 4.OLD RISER DIAGRAM SHOWED NOTE SAID | | | "TIE INTO EXISTINGBUILDING SANITARY AT | | | RESTROOMS ABOVE 6TH FLOOR CEILING", | | | REVISED PLAN READS,"ABOVE 5TH FLOOR | | | CEILING. SUITE IS ON THE 7TH FLOOR. THE | | | EXISTING 4" SANITARY PIPE AT BATHROOMS | | | SHOULD NOT BE CAPPED OFF, THAT STACK | | | BECOMES A VENT ON THE TOP FLOOR AND GOES | | | OUT THE ROOF. | | | ONE SET OF DRAWINGS MARKED IN RED. | | | PLUMBING PLAN REVIED BY; | | | JOHN LEECH | | | 805-6695 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|