| Date |
Text |
| 2005-07-07 00:00:00 | ******** UNSAT ********* |
| | |
| | PLEASE SEE SOME NOTES FROM FIRST REVIEW |
| | AND SOME CHANGES IN PLANS HAVE COMMENTS. |
| | |
| | 1)NOTE: PLEASE SEE NOTE#1 FROM PREVIOUS |
| | REVIEWED REQUESTED THE ENGINEER |
| | RESPONSIBLE FOR DESIGN TO SIGN AND SEAL |
| | PLANS. THIS WAS DONE, HOWEVER ENGINEER'S |
| | TITLE BLOCK WAS REMOVED?? |
| | PLEASE SEE FAC 61G15-23.002 AND FS |
| | 471.023 FOR REQUIRED TITLEBLOCK AND |
| | INFORMAITON REQUIRED ON SAID TITLE |
| | BLOCK. |
| | |
| | 2)NOTE: PLEASE SEE RISER DIGRAM HAS NOW |
| | BEEN REVISED, PLEASE SEE PANEL "LB" IS |
| | STILL SHOWN AS MLO. PLEASE SEE RISER |
| | MENTIONS 175A BRKR. PLEASE SEE PANEL |
| | "LA" INDICATES BEING A 225A MCB? PLEASE |
| | CORRELATE. |
| | PLEASE SEE PANEL "LB" DOES NOT INDICATE |
| | ANY OCP FEEDING "LA"? IS THIS A FEED |
| | THRU LUGS PANEL? |
| | 408.16,240.21 ETC. |
| | |
| | 3)NOTE: PLEASE SEE PANEL 4H STILL |
| | INDICATES 200A OCP FEEDING 45KVA |
| | TRANSFORMER? ON #6 AWG. |
| | PLEASE SEE MAX OCP IN 450.3(125%). |
| | PLEASE ALSO SEE 240.4,310.16 FOR SIZING |
| | OF CONDUCTORS. |
| | |
| | 4)NOTE: PLEASE SEE 210.8B3 FOR |
| | KITCHEN/BRK RM RECEPTS WHICH REQUIRES |
| | ALL 15- AND 20-AMPERE, 125-VOLT |
| | RECEPTACLES IN NONDWELLING-TYPE KITCHENS |
| | TO BE GFCI PROTECTED. THIS REQUIREMENT |
| | APPLIES TO EACH AND EVERY 15- AND |
| | 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE, |
| | WHETHER OR NOT THE RECEPTACLE SERVES |
| | COUNTERTOP APPLIANCES. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETSFOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |