| 2005-05-20 00:00:00 | ********UNSAT *********** |
| | |
| | 1)NOTE: PLEASE SEE PLANS ARE CONTAINING |
| | A TITLE BLOCK OF SORTS WHICH REFERENCE A |
| | PE FOR PLANS, HOWEVER THE PE SHOWN HAS |
| | NOT SIGNEDAND SEALED PLANS.?? |
| | PLEASE SEE IF PE IS RESPONSIBLE FOR |
| | DESIGNAND ON PLANS , THEN THAT PE MUST |
| | SIGN,DATE AND SEALED PLANS. FS471.025 |
| | |
| | PLEASE SEE SEAL FOR ARCH (IF ARCH SEALS |
| | PLANS) IS CLEAR AND VISABLE WIH |
| | INFORMATION REQUIRED ON SEAL FOR P, M |
| | AND E SHEETS. |
| | FS 481.221 FAC 61G1-16.003 |
| | |
| | 2)NOTE: PLEASE CLARIFY MEANS OF DISC AND |
| | OCP FROM BUS RISER? |
| | PLEASE SEE 4H IS SHOWN AS MLO? THERE |
| | SHALL BE A MAIN AND OCP ON THE LINE SIDE |
| | 4H. |
| | PLEASE SEE PANELS ON THE SECONDARY SIDE |
| | OF THE TRANSFORMER ARE BOTH SHOWN AS |
| | MLO. |
| | PLEASE SEE THESE SHALL BOTH HAVE MCB'S |
| | INSTALLED. |
| | 215.5,408.16,240.21 ETC. |
| | |
| | 3)NOTE: PLEASE SEE 200A OCP SHOWN FOR |
| | MAIN SIDE OF 45 KVA TRANSFORMER DOES NOT |
| | MEET 450.3. A MAX OCP OF 125% IS ONLY |
| | PERMITTED. |
| | |
| | PLEASE BE SURE TO SEE ANY POSSIBLE |
| | COMMENTS FROM OTHER REVIEWER(S) WHICH |
| | MAY AFFECT ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AN |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |