2005-05-20 00:00:00******** UNSAT *********
  
 1)NOTE: PLEASE SEE FAC 61G15-23.002
 WHICH REQUIRES THE "PRINTED NAME AND
 LICENSE #" OF PE.
  
 2)NOTE: PLEASE SEE ON ORIGINAL PLANS THE
 EQUIPMENT GROUNDING WHICH IS INSTALLED
 AFFTER THE FIRST MEANS OF DISC PER
 250.24 WAS REMOVED, HOWEVER THIS SET OF
 PLANS SHOWS THE CONDUCTORS INSTALLED FOR
 "EXISTING SERVICE".
 250.6,250.24
  
 3)NOTE: PLEASE AN EQUIPMENT GROUNDING
 APPEARS TO BE SHOWN AFTER THE MEANS OF
 DISC TO PANEL "CW", HOWEVER RISER DOES
 NOT INCLUDE EQUIPMENT GRND THROUGH TO
 PANEL??
 250.110,250.122
  
 4)NOTE: PLEASE CLARIFY RISER SHOWS A
 GROUNDING ATTACHMENT AT PANEL "CW",
 HOWEVER NO CONNECTION POINTS ARE SHOWN.?
 250.50?
  
 5)NOTE: PLEASE PROVIDE/CLARIFY IF LOAD
 FOR PANEL "CW" WAS INCLUDED ON EXSITING
 SERVICE UNDER PERMIT FOR GAS STATION/
 CONV STORE.
 215.5,220
  
 6)NOTE: PLEASE SEE SHEETS DONE BY THE
 ENGINEER ARE ALSO SIGNED AND SEALED BY
 THE ARCH?
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD/VOIDED SHEETS SHALL BE
 SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  