| Date |
Text |
| 2005-05-20 00:00:00 | ******** UNSAT ********* |
| | |
| | 1)NOTE: PLEASE SEE FAC 61G15-23.002 |
| | WHICH REQUIRES THE "PRINTED NAME AND |
| | LICENSE #" OF PE. |
| | |
| | 2)NOTE: PLEASE SEE ON ORIGINAL PLANS THE |
| | EQUIPMENT GROUNDING WHICH IS INSTALLED |
| | AFFTER THE FIRST MEANS OF DISC PER |
| | 250.24 WAS REMOVED, HOWEVER THIS SET OF |
| | PLANS SHOWS THE CONDUCTORS INSTALLED FOR |
| | "EXISTING SERVICE". |
| | 250.6,250.24 |
| | |
| | 3)NOTE: PLEASE AN EQUIPMENT GROUNDING |
| | APPEARS TO BE SHOWN AFTER THE MEANS OF |
| | DISC TO PANEL "CW", HOWEVER RISER DOES |
| | NOT INCLUDE EQUIPMENT GRND THROUGH TO |
| | PANEL?? |
| | 250.110,250.122 |
| | |
| | 4)NOTE: PLEASE CLARIFY RISER SHOWS A |
| | GROUNDING ATTACHMENT AT PANEL "CW", |
| | HOWEVER NO CONNECTION POINTS ARE SHOWN.? |
| | 250.50? |
| | |
| | 5)NOTE: PLEASE PROVIDE/CLARIFY IF LOAD |
| | FOR PANEL "CW" WAS INCLUDED ON EXSITING |
| | SERVICE UNDER PERMIT FOR GAS STATION/ |
| | CONV STORE. |
| | 215.5,220 |
| | |
| | 6)NOTE: PLEASE SEE SHEETS DONE BY THE |
| | ENGINEER ARE ALSO SIGNED AND SEALED BY |
| | THE ARCH? |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONE SET OF OLD/VOIDED SHEETS SHALL BE |
| | SUBMITTED FOR REFERENCE ONLY. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |