Plan Review Notes For Permit 05050417
Permit Number 05050417
Review Stop P
Sequence Number 1
Notes
Date Text
2005-05-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1. SHOW OPENING FOR WATER CLOSET.
 MINIMUM 15" OFF THE WALL AND 15" OFF THE
 SHOWER TO CENTERLINE OF FIXTURE. MINIMUM
 30" OPENING REQUIRED. SECTION 405.3.1.
 2. SHOW SIZE OF SHOWER STALL. MINIMUM
 900 SQUARE INCHES. MINIMUM 30" INSIDE
 FINISH WIDTH. SECTION 417.4.
 3. SANT. RISER DIAGRAM DOES NOT REFLECT
 THE FLOOR PLAN. ONLY ONE LAV SHOWN ON
 THE RISER DIAGRAM, AND TWO LAVS ARE
 SHOWN ON THE FLOOR PLAN. SECTION
 104.2.1.
  
 REVIEW BY KEN STEVENS