| Plan Review Notes For Permit 05050382 |
| Permit Number |
05050382 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-05-27 00:00:00 | DENIED | | | REFERENCE: FBC-2001 424.2 SWIMMING POOLS | | | | | | 1. FBC-2001 424.2.9 WATER SUPPLY, LOCAL | | | ORD. #2853-95, BACKFLOW REQUIRED ON THE | | | WATER SERVICE. (ADD TO NOTES) | | | 2. FBC-2001 424.2.12.1 PRESSURE TESTS. | | | PER MANUFACTURE RECOMMENDATIONS, NO AIR | | | TEST SHALL BE APPROVED FOR PVC PIPE AND | | | FITTINGS. (ADD TO NOTES) | | | 3. FBC-2001 424.2.13.2 JOINTS AND | | | CONNECTIONS, FBC PLMG. SEC 605.21 PURPLE | | | PRIMER REQUIRED ON PVC PIPING. (ADD TO | | | NOTES). | | | 4. MANUF. SPECIFICATION SHEETS DO NOT | | | SHOW POSITIVE MEANS TO RETAIN WATER | | | SHOULD THE PUMP SHUT OFF. AN EXTERIOR | | | HARTFORD LOOP IS REQUIRED. SECTION | | | 424.2.14.2 | | | 5. FBC-2001 424.2.15 GAS PIPING SHALL | | | COMPLY WITH FBC FUEL GAS. SEPARATE PLANS | | | AND PERMIT REQUIRED. (ADD TO NOTES) | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | |
|