| 2005-08-27 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05050354 |
| | ADD: 3700 BROADWAYY |
| | CONT: WEST |
| | TEL: (561)718-8656 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | |
| | |
| | 1) COMMENT# 3) FROM THE PREVIOUS REVIEW, |
| | PROVIDE ADDITIONAL INFORMATION, |
| | PROVIDE MIN. BUILDING TYPE OF DESIGN, |
| | (TABLE 500/ 600) IF ANY AREA INCREASES |
| | WERE TAKEN? PLANS INDICATE THIS TO BE A |
| | TYPE IV/ 1 HR PROTECTED/ FULLY |
| | SPRINKLERED BUILDING. |
| | 1A) FOR THIS BUILDING TO BE CONSIDERED |
| | TYPE IV CONSTRUCTION, LOOK AT TABLE 600, |
| | NON BEARING WALLS, NO COMBUSTIBLE IN |
| | WALLS SHEET A-4 STILL INDICATES THE USE |
| | OF PLYWOOD AS A SUBSHEATHING. THIS |
| | BUILDING CAN BE CONSIDERED A TYPE VI |
| | UNPROTECTED/ FULLY SPRINKLERED BUILDING, |
| | THIS WILL ALLOW THE WOOD INFILL IN THE |
| | EXTERIOR WALLS AND PROVIDE AN ALLOWABLE |
| | 24,000 SQ FT BUILDING. |
| | 1B) CLASSIFICATION OF THIS BUILDING AS A |
| | TYPE IV 1HR PROTECTED BUILDING ALSO |
| | CREATES A PROBLEM WITH THE ROOF |
| | SHEATHING, TABLE 600 REQUIRES THEROOF TO |
| | BE 1 HR RATED, FOOTNOTE "E" DOES ALLOW |
| | ONE STORY BUILDINGS TO USE FIRE |
| | RETARDANT WOOD SHEATHING. TYPE VI |
| | UNPROTECTED/ FULLY SPRINKLERED HAS NO |
| | SUCH LIMITATIONS WITH THE ROOF. |
| | |
| | 2) COMMENT 6B FROM THE PREVIOUS REVIEW, |
| | 6B)PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 6C)FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | ******* E) ROOF ASSEMBLIES MISSING FL |
| | COVER SHEET, NOA GOOD FOR STEEL DECK |
| | PLANS INDICATE T&G DECK.**************** |
| | |
| | 3) ALTHOUGH THE ENERGY CALCULATIONS ARE |
| | SEALED THEY INDICATE THE WORK BEING |
| | COMPLETED IS IN RIVIERA. |
| | |
| | 4) COMENT# 8 FROM THE PREVIOUS |
| | REVIEWDEALS WITH INFILL FOR THE EXTERIOR |
| | WALLS, DEPENDING ON THE RESULTS OF |
| | QUESTION # 1 THIS MAY OR MAY NOT BE A |
| | ISSUE. SHEET A-4, FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | 4A) EXTERIOR WALL DETAILS INDICATE THE |
| | USE OF WOOD INFILL, DEPENDING ON THE |
| | CLASSIFICATION OF THIS BUILDING THIS MAY |
| | BE A ISSUE. THE ITEMS IN CONCERN ARE THE |
| | DESIGNER OF RECORD DOES NOT INDICATE HOW |
| | THE 2X8 PT PLATE WILL BE ANCHORED INTO |
| | THE EXISTING STRUCTURE? |
| | |
| | 5) PLEASE PROVIDE FIRE SPRINKLER PLANS |
| | OF EXISTING SYSTEM AND IF ANY NEW HEADS |
| | ARE BEING INSTALLED. PLANS WILL BE |
| | REQUIRED SINCE IT APPEARS THAT YOU ARE |
| | TAKING THE EXCEPTION TO 1005.4.2 |
| | EXECEPTION (1) |
| | 1. EMERGENCY ESCAPE AND RESCUE OPENINGS |
| | SHALL NOT BE REQUIRED IN BUILDINGS |
| | PROTECTED THROUGHOUT BY AN APPROVED |
| | AUTOMATIC SPRINKLER SYSTEM. |
| | |
| | 6) NEW COMMENT THE ORIENTATION OF |
| | BROADWAY IS ON THE WRONG SIDE OF THE |
| | BUILDING, CORRECTING WILL HELP IN TABLE |
| | 600 ISSUES, SEE A-1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |