| Date |
Text |
| 2005-06-16 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1. PLANS SHALL BE ROUTED TO THE PALM |
| | BEACH COUNTY HEALTH UNIT DIVISION OF |
| | ENVIROMENTAL HEALTH FOR REVIEW PRIOR TO |
| | RESUBMITTING. EACH SET OF PLANS |
| | RESUBMITTED FOR REVIEW BY CITY WPB SHALL |
| | BE STAMPED BY HEALTH DEPT REVIEWER. |
| | SECTION 101.4.7. |
| | 2. THE GREASE INTERCEPTOR SHALL BE SIZED |
| | BY RODNEY COMPO, ENVIRONMENTAL |
| | COMPLIANCE MANAGER. CONTACT MR. COMPO |
| | (561) 822-2272, E-MAIL [email protected], |
| | OR FAX (561) 653-2692. SUBMIT THE |
| | DETERMINATION SHEET FROM MR. COMPO WITH |
| | PLANS WHEN RESUBMITTING. WASTE ORD. |
| | #2938-96. |
| | 3. INDICATE IF THERE WILL BE COOKING OF |
| | MEALS AT THE KITCHEN FACILITY. WHAT TYPE |
| | OF MEALS WILL BE SERVED? SECTION |
| | 104.2.1. |
| | 4. INDICATE THE AGE OF THE STUDENTS AS |
| | THIS WILL AFFECT THE REQUIREMENTS OF THE |
| | SCHOOL. SECTION 104.2.1. |
| | 5. SUBMIT CALCULATIONS FOR MINIMUM |
| | FACILITIES PER TABLES 1003.1 & 403.1. |
| | INDICATE THE SQUARE FOOTAGE OF EACH |
| | OCCUPANCY. |
| | 6. SHT A-2 BOYS BATHROOM, URINALS SHALL |
| | NOT BE SUBSTITUTED FOR MORE THAN 50% OF |
| | THE REQUIRED WATER CLOWETS. - DEPENDING |
| | ON THE RESPONSE TO COMMENT #5 ABOVE, |
| | THIS MAY OR MAY NOT APPLY. |
| | 7. SHT A-3 THE FOLLOWING INFORMATION FOR |
| | CHAPTER 11 SHALL BE SHOWN OR INDICATED |
| | ON THE PLANS: |
| | FOR WATER CLOSETS: |
| | A. 11-4.16.2 CLEAR FLOOR SPACE |
| | B. 11-4.16.3 HEIGHT (SHOWS MAX 20") |
| | C. 11-4.16.5 FLUSH CONTROLS |
| | D. 11-4.16.6 DISPENSERS |
| | FOR URINAL: |
| | A. 11-4.18.2 HEIGHT |
| | B. 11-4.18.3 CLEAR FLOOR SPACE |
| | C. 11-4.18.4 FLUSH CONTROLS |
| | FOR LAVS: |
| | A. 11-4.19.3 CLEAR FLOOR SPACE |
| | B. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | C. 11-4.19.5 FAUCETS |
| | FOR SHOWERS: |
| | A. 11-4.21.2 SIZE & CLEARANCES (SHOW |
| | LENGTH & WIDTH) |
| | B. 11-4.21.3 SEAT (TO COMPLY WITH FIG. |
| | 36 AND SHOW CONTROL LOCATION). |
| | C. 11-4.21.5 CONTROLS |
| | D. 11-4.21.6 SHOWER UNIT |
| | E. 11-4.21.7 CURBS |
| | DRINKING FOUNTAIN: |
| | A. 11-4.15.2 SPOUT HEIGHT |
| | B. 11-4.15.3 SPOUT LOCATION |
| | C. 11-4.15.4 CONTROLS |
| | D. 11-4.15.5 CLEARANCES/CLEAR FLOOR |
| | SPACE |
| | E. 11-4.1.3(10)(A) FOR THOSE WHO HAVE |
| | DIFFICULTY BENDING OR STOOPING. (IF THIS |
| | IS A SINGLE ELEVATION UNIT - NOT |
| | REQUIRED IF HIGH/LOW DRINKING FOUNTAIN). |
| | 8. AN RPZ BACKFLOW IS REQUIRED ON THE |
| | WATER SERVICE TO THE BUILDING. SECTION |
| | 608.13.2. |
| | 9. SHT P-1 WATER RISER DIAGRAM. ALL |
| | WATER HAMMER ARRESTORS SHALL BE LOCATED |
| | NEAR THE FIXTURE IN AN "EFFECTIVE RANGE" |
| | NOT IN THE CEILING AS SHOWN IN SOME |
| | AREAS. PDI-WH 201. |
| | 10. WATER HEATER DETAIL. THERMAL |
| | EXPANSION CONTROL IS REQUIRED, AND A |
| | VACUUM RELIEF VALVE IS REQUIRED FOR ALL |
| | BOTTOM FED WATER HEATERS. SECTIONS |
| | 607.3.2. AND 504.2. |
| | 11. THE FOLLOWING ARE GAS PERMIT |
| | APPLICTION REQUIREMENTS: |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES. |
| | C. TYPE OF GAS, (LP OR NATURAL) |
| | D. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2. |
| | F. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | G. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND |
| | APPURTENANCES PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |
| | |