| 2005-06-23 00:00:00 | DENIED: |
| | 1.PLAN SHEET AC-1 DUCT PENTRATING WALL |
| | BETWEEN THE STORAGE ROOM AND CLASS ROOM |
| | #6 INDICATES A FIRE DAMPER.ACCORDING |
| | TO PLAN SHEET A-2 THE FIRE DAMPER SHOULD |
| | BE LOCATED BETWEEN THE CORRIDOR AND THE |
| | STORAGE ROOM, PLEASE CLARIFY. |
| | |
| | 2.PROVIDE CURB DETAIL & TERMINATION |
| | LOCATION FOR EXHAUST FANS.PROVIDE |
| | DISTANCE FROM FRESH AIR INTAKES ON THE |
| | RTU'S. |
| | |
| | 3.PROVIDE INFORMATION FOR EXHAUST DUCT |
| | TO THE DRYER LOCATED IN THE "HOUSEHOLD |
| | ROOM".INDICATE DUCT SIZE, MATERIAL, |
| | AND TERMINATION.PLEASE NOTE, PER 2001 |
| | FBC(M) 504.6, MAKEUP AIR SHALL BE |
| | PROVIDED FOR INTALLATIONS THAT EXHAUST |
| | GREATER THAN 200 CFM. |
| | |
| | 4.PLAN SHEET AC-1 INDICATES RETURN AIR |
| | IN THE LAUNDRY AREA.WILL THIS BE |
| | RECIRCULATED? |
| | |
| | 5.PROVIDE SPECIFICATION ON THE DRYER. |
| | |
| | 6.INDICATE WHAT KIND OF FOOD PREP WILL |
| | BE TAKING PLACE.PLAN SHEET A-2 |
| | INDICATES HOT & COLD FOOD.PLEASE |
| | INDICATE ANY "COOKING" EQUIPMENT OR |
| | APPLIANCES. |
| | |
| | 7.PLAN SHEET AC-1 INDICATES |
| | DISHWASHER, PLEASE PROVIDE SUBMITTAL |
| | DATA.WILL A HEAT HOOD BE REQUIRED? |
| | |
| | 8.PROVIDE DETAIL FOR SECURING ROOF |
| | CURBS & EQUIPMENT.SHOW COMPLAINCE WITH |
| | 2001 FBC 1606, FOR REQUIRED WIND LOADS. |
| | |
| | 9.PLANS DO NOT INDICATE CONDENSATE |
| | LAYOUT, MATERIAL, AND TERMIANTION. |
| | TERMINATION SHALL COMPLY WITH 2001 |
| | FBC(M)307.2.1.AND FBC 1503.4.4. |
| | |
| | 10.PROVIDE ADDTIONAL INFORMATION FOR |
| | THE GENERATOR ON PLAN SHEET P-2. |
| | PROVIDE MANUFACTURER'S SUBMITTAL DATA. |
| | |
| | 11.PLEASE INDCIATE ALL APPLIANCES THAT |
| | WILL UTILIZE THE GAS.PLEASE INDICATE |
| | NATURAL OR LP GAS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561)805-6719. |
| | |