Plan Review Notes
Plan Review Notes For Permit 05050326
Permit Number 05050326
Review Stop E
Sequence Number 3
Notes
Date Text
2005-09-04 00:00:00********** UNSAT 3RD REVIEW *********
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW AND PLEASE SEE SOME NEW NOTES DUE
 TO CHANGES IN PLANS ONCE AGAIN.
  
  
 1)NOTE: PLEASE SEE PLANS NOW HAVE
 REVISED TITLE BLOCKS SIGNED AND SEALED
 BY AN ENGINEER, HOWEVER PLEASE SEE SOME
 ELECTRICAL SHEETS CONTAIN THE PRINTED
 ENGINEER OF RECORD TO BE GUILLERMO NUNEZ
 AND PLANS ARE SIGNED AND SEALED BY A
 DIFFERENT ENGINEER???
 PLEASE SEE FAC 61G15-23.002 FOR REQUIRED
 INFORMATION TO BE ON TITLE BLOCKS.
 ***************************************
 PLEASE ALSO SEE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER REQUIRED FOR
 ENGINEERING FIRM AS SHOWN. FS 471.023
 PLEASE KNOW, TITLE BLOCKS ARE REQUIRED
 TO BE CORRECTED FOR ALL SHEETS AND FOR
 ALL TRADES, WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
 PLEASE SEE A SIGNED, DATED AND SEALED
 LETTER FROM ARCHITECT WAS NOT SUBMITTED
 AS PREVIOUSLY REQUESTED.
 NOTORY SHOULD BE SURE TO NOTORIZE LETTER
 AS REQUIRED UNDER FS 117.05
 (SEE NOTE #2)
  
 ***************************************
  
 PLEASE SEE ONE ENTIRE SET OF PLANS (ALL
 TRADES) IS BEING RETAINED AND WILL NOW
 BE TURNED OVER TO THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS ANDSTATES LEGAL
 COUNSEL TO THE FLORIDA BOARD OF
 ARCHITECTS FOR REVIEW OF LICENSING
 DISCREPANCIES AND CODE COMPLIANCE.
 PLEASE SEE A REVIEW MAY ALSO BE DONE FOR
 PLANS AND CODE COMPLIANCE INFORMATION.
 PLEASE SEE THE FOLLOWING COMMENT.
  
 ****************************************
  
 2)NOTE: PLEASE SEE THAT NOTES WERE GIVEN
 BY MULTIPLE REVIEWERS ON PREVIOUS REVIEW
 WITH REFERENCE TO FS 553.80(2)(B) WITH
 RESPECT TO DESIGN PROFESSIONALS AND
 PLANS BEING REVIEWED THREE OR MORE TIMES
 WITH ANY OF THE SAME COMMENTS NOT BEING
 ADDRESSED. PLEASE SEE COMMENTS BELOW AS
 SOME COMMENTS FROM PREVIOUS TWO REVIEWS
 STILL NEED TO BE ADDRESSED. PLEASE SEE
 THAT A 4X FEE HAS NOW BEEN ASSESSED FOR
 PLAN REVIEW PER ABOVE MENTIONED FS
 553.80 AND A FEE OF $1500.00 MUST BE
 PAID BEFORE THE PLANS MAY BE SUBMITTED
 FOR NEXT REVIEW.
 PLEASE KNOW, IF PLANS COME BACK IN FOR
 4TH REVIEW WITH ANY OF THE SAME COMMENTS
 FROMPREVIOUS 3 REVIEWS NOT ADDRESSED
 AN ADDTIONAL 4X FEE WILL BE ASSESSED.
 THIS STANDS FOR ALL REVIEWS AFTER 3RD
 SUCH REVIEW.
  
 2)NOTE: PLEASE PROVIDE A SIGNED, DATED
 AND SEALED NOTORIZED LETTER FOR LEGAL
 SIGNATURE VERIFICATION OF ARCHITECT.
 OTHER SHEETS APPEAR TO BE SIGNED WITH
 INITIALS, IF INDEED THIS IS THE LEGAL
 SIGNATURE, PLEASE PROVIDE LETTER AS
 STATED ABOVE. PLEASE BE SURE LETTER IS
 PROPERLY NOTORIZED AS REQUIRED UNDER FS
 117.
  
 3)NOTE:PLEASE SHOW LOCATION OF
 EXISTING SERVICE ON "SERVICE POWER SITE
 PLAN".
 PLEASE SEE THE "SITE POWER PLAN" HAS NOW
 BEEN REMOVED AND GROUPING OF MAINS CAN
 NOT BE VERIFIED AT THIS TIME.
 PLEASE SEE GROUPING OF MAINS WILL BE
 REQUIRED 230.72.
  
 4)NOTE: PLEASE SEE THAT SERVICE IS NOW
 INDICATING A NEW 600A SERVICE, MAIN DISC
 AND PANEL.
 PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTORS FROM 600A MAIN TO 600A PANEL.
 PLEASE SEE 250.122 FOR SIZING FOR EACH
 OF THE THREE PARALLEL RUNS SHOWN.
 250.110
 PLEASE ALSO SEE MISSING EQUIPMENT
 GROUNDING METHOD TO SUB PANEL "B".
 *NOTE*EMT MAY NOT BE USEDAS AN
 EQUIPMENT GROUNDING METHID UNLESS ALL
 FITTINGS USEDARE THE NEW FITTINGS NOW
 LISTED AS APPROVED FOR "EQUIPMENT
 GROUNDING"
  
 5)NOTE: PLEASE CORRELATE AWG SHOWN FOR
 SAME SUB FEED TO PANEL "B". #3, #1?
 240.4,310.16,215.5
  
 6)NOTE: PLEASE SEE SPECS/MANUFACTURE
 SHEETS FOR ALL TANNING BEDS/ EQUIPMENT
 PROPOSED WAS NOT SUBMITTED FOR REVIEW OF
 THE LISTINGS REQUIRED PER NEC 110.3B,
 ALL LISTINGS MUST BE BY A NATIONAL
 RECOGNIZED TESTING LABORATORY. (NRTL).
 PLANS MENTIONS INSTALLATION OF
 TRANSFORMER FOR THIS EQUIPMENT, HOWEVER
 THIS IS NOT SHOWN ON PLANS AND EQUIPMENT
 CAN NOT BE VERIFIED FOR INSTALLATION.
  
 7)NOTE: PLEASE SEE 250.50, PLEASE SHOW
 COLD WATER PIPE PART OF GROUNDING
 ELECTRODE SYSTEM. (IF METAL) RISER SHOWS
 A CONNECTION, HOWEVER THIS IS NOT CLEAR
 OR LABELED AS TO WHAT CONNECTION THIS
 MAY BE.
 PLANS MENTIONS TO EXISTING GROUNDING
 ELECTRODE SYSTEM, YET THIS CAN NOT
 VERIFIED AS NO DETAIL AS REQUIRED PER
 250.50 IS SHOWN.
 PLEASE SEE FBC 104.2.1 WHICH STATES
 "TECHNICAL CODES SHALL NOT BE QUOTED IN
 LEIU OF PLANS/DETAILS"
  
  
 8)NOTE: PLEASE SEE ON TWO PREVIOUS
 REVIEWS, IT WAS REQUESTED TO "REMOVE ALL
 OLD/VOIDED SHEETS" AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 PLEASE SEE ALL SETS HAVE COME BACK IN
 ONCE AGAIN WITH ALL OLD/VOIDED SHEETS
 STILL IN SETS.
 THIS MUST BE DONE BEFORE SUBMITTING
 PLANS FOR NEXT REVIEW.
 PLEASE BEAR IN MIND, ONE COMPLETE SET OF
 PLANS ARE BEING RETAINED BY THIS OFFICE.
  
 PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]