| 2005-08-10 00:00:00 | ********** UNSAT 2ND REVIEW ********* |
| | |
| | PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW AND PLEASE SEE SOME NEW NOTES DUE |
| | TO CHANGES IN PLANS. |
| | |
| | |
| | 1)NOTE: PLEASE SEE ALL PLANS SHALL |
| | CONTAIN TITLE BLOCKS FOR ARCHITECT(S), |
| | ENGINEER(S) INTERIOR DEISGNER ALONG WITH |
| | ALL FIRM'S. |
| | PLEASE SEE MISSING LICENSE INFORMATION |
| | REQUIRED PER FAC 61G1-16.004, FS |
| | 481.219. |
| | PLEASE SEECONSULTING ENGINEER OF |
| | RECORD HAS NOW BEEN REMOVED FROM TITLE |
| | BLOCK? |
| | PLEASE SEE FS 471.025, THE ENGINEER OF |
| | RECORD SHALL SIGN, DATE AND SEAL ALL |
| | PLANS HE IS RESPONSIBLE FOR. NO OTHER |
| | PERSON MAY SIGN AND SEAL ANOTHER'S WORK. |
| | FS 481,471 |
| | |
| | PLEASE SEE PREVIOUS NOTE MENTIONED, THE |
| | ABOVE REQUIREMENTS ARE REQUIRED FOR ALL |
| | TITLE BLOCKS AND FOR ALL TRADES WHETHER |
| | OR NOT COMMENT IS MADE BY ANY OTHER |
| | REVIEWER(S). |
| | |
| | PLEASE SEE ONE SET OF ELECTRICAL PLANS |
| | HAVE NOW BEEN RETAINED FOR FILE FOR ANY |
| | FUTURE REFERENCE. |
| | |
| | 2)NOTE: PLEASE SEE PLANS HAVE NOW COME |
| | BACK WITH OUT ANY OF THE ELECTRICAL |
| | PLANS SIGNED, DATED OR SEALED? |
| | FS 481.221,471.025 |
| | |
| | 3)NOTE: PLEASE PROVIDE A SIGNED, DATED |
| | AND SEALED NOTORIZED LETTER FOR LEGAL |
| | SIGNATURE VERIFICATION OF ARCHITECT. |
| | OTHER SHEETS APPEAR TO BE SIGNED WITH |
| | INITIALS, IF INDEED THIS IS THE LEGAL |
| | SIGNATURE, PLEASE PROVIDE LETTER AS |
| | STATED ABOVE. PLEASE BE SURE LETTER IS |
| | PROPERLY NOTORIZED AS REQUIRED UNDER FS |
| | 117. |
| | |
| | 4)NOTE: PLEASE SHOW LOCATION OF EXISTING |
| | SERVICE ON "SERVICE POWER SITE PLAN". |
| | PLEASE SEE GROUPING OF MAINS WILL BE |
| | REQUIRED 230.72. |
| | |
| | 5)NOTE: PLEASE CORRELATE RISER, LEGEND |
| | FOR RISER AND PLANS. |
| | PLEASE SEE FEEDERS FOR 400A PANEL "A". |
| | 215.5 |
| | |
| | 6)NOTE": PLEASE CORRELATE PANELS, LEGEND |
| | FOR RISER AND RISER. |
| | PLEASE SEE PANEL "B". 100A, 125A ?? |
| | 215.5 |
| | |
| | 7)NOTE: PLEASE CORRELATE AWG SHOWN FOR |
| | SMAE SUB FEED TO PANEL "B". #2, #1? |
| | 215.5 |
| | |
| | 8)NOTE: PLEASE SEE SPECS/MANUFACTURE |
| | SHEETS FOR ALL TANNING BEDS/ EQUIPMENT |
| | PROPOSED WAS NOT SUBMITTED FOR REVIEW OF |
| | THE LISTINGS REQUIRED PER NEC 110.3B, |
| | ALL LISTINGS MUST BE BY A NRTL. |
| | |
| | 9)NOTE: PLEASE INDICATE NEW OR EXISTING |
| | SIGN CIRCUIT. 600.5 |
| | |
| | 10)NOTE: PLEASE SEE 250.50, PLEASE SHOW |
| | COLD WATER PIPE PART OF GROUNDING |
| | ELECTRODE SYSTEM. (IF METAL) RISER SHOWS |
| | A CONNECTION, HOWEVER THIS IS NOT CLEAR |
| | OR LABELED AS TO WHAT CONNECTION THIS |
| | MAY BE. |
| | |
| | 11)NOTE: PLEASE SEE COPY OF FS |
| | 553.80(2)(B) WITH RESPECT TO THE DESIGN |
| | PROFESSIONAL. PLEASE SEE THIS IS A |
| | NOTICE GIVEN AT THIS TIME ONLY. |
| | |
| | PLEASE BE SURE TO SEE ANY POSSIBLE |
| | COMMENTS FROM OTHER TRADES WHICH MAY |
| | AFFECT ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS FROM |
| | SETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO COMPLETE SETS FOR REVIEW AND |
| | STMAPING. ONE SET OF ALL OLD/VOIDED |
| | SHEET SHALL BE SUBMNITTED FOR REFERENCE. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |