Plan Review Notes
Plan Review Notes For Permit 05050326
Permit Number 05050326
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2005-06-01 00:00:00****DENIED****
  
 1) PLEASE SEE ELECTRICAL REVIEW COMMENTS
 IN REGARDS TO FS AND FAC REQUIREMENTS.
  
 2) PLANS NOTE THAT THIS IS A FIRE
 SPRINKLERED BUILDING. SEPARATE SHOP
 DRAWINGS AND PERMITS ARE REQUIRED FOR
 THE FIRE SPRINKLER AND FIRE ALARM
 REMODELS IF APPLICABLE.
  
 3) LIFE SAFETY SHALL COMPLY WITH NFPA
 101, 2003 EDITION.
  
 4) 2A-10B,C RATED FIRE EXTINGUISHER(S)
 ARE REQUIRED AND SPACED NOT TO EXCEED
 75' TRAVEL DISTANCE.
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2951 OR 805-6722