| Date |
Text |
| 2005-05-19 00:00:00 | *************** UNSAT ************* |
| | |
| | 1)NOTE: PLEASE SEE MISSING LICENSE |
| | INFORMATION REQUIRED FOR ARCHITECTUAL |
| | AND ENGINEERING FIRMS. FAC 61G1-16.004, |
| | FAC 61G15-23.002, FS 471.023, AND FS |
| | 481.219. |
| | PLEASE SEE CERTIFICATE OF AUTHORIZATION |
| | #'S ARE REQUIRED FOR ALL SHEETS AND FOR |
| | ALL TRADES WHETHER OR NOT COMMENT IS |
| | MADE BY OTHER REVIEWER(S). |
| | PLEASE SEE THIS IS ALSO REQUIRED FOR ID |
| | PLANS AS THEY ALSO FALL UNDER SAME FS |
| | AND FAC'S. |
| | |
| | 2)NOTE: PLEASE SEE PLANS CONTAINING |
| | TITLE BLOCK FOR ENGINEER OF DESIGN, |
| | SHALL BE SIGNED, DATED AND SEALEDFS |
| | 471.025 |
| | |
| | 3)NOTE: PLEASE ALSO SEE THE ABOVE |
| | REFERENCED STATUES AND ADMINISTRATIVE |
| | CODES WHICH REQUIRES THE SEAL TO BE |
| | RAISED, CLEAR AND VISABLE WITH ALL |
| | INFORMAITON REQUIRED ON SAID SEAL. |
| | PLEASE SEE SIGNATURE MUST ALSO BE LEGAL |
| | SIGNATURE. |
| | |
| | 4)NOTE: PLEASE CORRELATE RISER, PLANS |
| | AND RISER LEGEND FOR SIZE OF A/C DISC |
| | AND OCP. |
| | 125A?100A? |
| | 215.5 |
| | |
| | 5)NOTE: PLEASE SEE 230.2 FOR ADDITIONAL |
| | SERVICES PERMITTED. PLEASE SEE NEW |
| | PROPOSED SERVICE DOES NOT SEEM MEET |
| | REQUIREMENTS OF 230.2. PLEASE PROVIDE |
| | MORE INFORMATION FOR PROPOSED NEW |
| | SERVICE FROM FPL. PLEASE SEE THIS WILL |
| | REQUIRED WRITTEN PERMISSION BY THE AHJ |
| | AND FPL. |
| | |
| | 6)NOTE: PLEASE CLARIFY WASHER/DRYER LOAD |
| | AND CIRCUIT SIZE. ARE THESE BOTH GAS? |
| | |
| | 7)NOTE: PLEASE SEE CONDUCTORS NOTED FOR |
| | 400A MAIN/PANEL ECT. |
| | DOES NOT MEET 240.4,310.16 ETC. |
| | |
| | 8)NOTE: PLEASE CLARIFY EQUIPMENT GROUNDI |
| | MEANS BETWEEN ALL PANEL/ EQUIPMENT. |
| | PER 250.110,250.24,250.122 ETC. |
| | |
| | 9)NOTE: PLEASE SUBMIT MANUFACTURE SPEC |
| | SHEETS FOR TANNING EQUIPMENT SHOWING |
| | LISTINGS BY A NRTL. |
| | 110.21 |
| | |
| | PLEASE BE AWARE OF POSSIBLE COMMENTS |
| | FROM OTHER REVIEWER(S) WHICH MAY HAVE AN |
| | AFFECT ON ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |