Plan Review Notes
Plan Review Notes For Permit 05050326
Permit Number 05050326
Review Stop E
Sequence Number 1
Notes
Date Text
2005-05-19 00:00:00*************** UNSAT *************
  
 1)NOTE: PLEASE SEE MISSING LICENSE
 INFORMATION REQUIRED FOR ARCHITECTUAL
 AND ENGINEERING FIRMS. FAC 61G1-16.004,
 FAC 61G15-23.002, FS 471.023, AND FS
 481.219.
 PLEASE SEE CERTIFICATE OF AUTHORIZATION
 #'S ARE REQUIRED FOR ALL SHEETS AND FOR
 ALL TRADES WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
 PLEASE SEE THIS IS ALSO REQUIRED FOR ID
 PLANS AS THEY ALSO FALL UNDER SAME FS
 AND FAC'S.
  
 2)NOTE: PLEASE SEE PLANS CONTAINING
 TITLE BLOCK FOR ENGINEER OF DESIGN,
 SHALL BE SIGNED, DATED AND SEALEDFS
 471.025
  
 3)NOTE: PLEASE ALSO SEE THE ABOVE
 REFERENCED STATUES AND ADMINISTRATIVE
 CODES WHICH REQUIRES THE SEAL TO BE
 RAISED, CLEAR AND VISABLE WITH ALL
 INFORMAITON REQUIRED ON SAID SEAL.
 PLEASE SEE SIGNATURE MUST ALSO BE LEGAL
 SIGNATURE.
  
 4)NOTE: PLEASE CORRELATE RISER, PLANS
 AND RISER LEGEND FOR SIZE OF A/C DISC
 AND OCP.
 125A?100A?
 215.5
  
 5)NOTE: PLEASE SEE 230.2 FOR ADDITIONAL
 SERVICES PERMITTED. PLEASE SEE NEW
 PROPOSED SERVICE DOES NOT SEEM MEET
 REQUIREMENTS OF 230.2. PLEASE PROVIDE
 MORE INFORMATION FOR PROPOSED NEW
 SERVICE FROM FPL. PLEASE SEE THIS WILL
 REQUIRED WRITTEN PERMISSION BY THE AHJ
 AND FPL.
  
 6)NOTE: PLEASE CLARIFY WASHER/DRYER LOAD
 AND CIRCUIT SIZE. ARE THESE BOTH GAS?
  
 7)NOTE: PLEASE SEE CONDUCTORS NOTED FOR
 400A MAIN/PANEL ECT.
 DOES NOT MEET 240.4,310.16 ETC.
  
 8)NOTE: PLEASE CLARIFY EQUIPMENT GROUNDI
 MEANS BETWEEN ALL PANEL/ EQUIPMENT.
 PER 250.110,250.24,250.122 ETC.
  
 9)NOTE: PLEASE SUBMIT MANUFACTURE SPEC
 SHEETS FOR TANNING EQUIPMENT SHOWING
 LISTINGS BY A NRTL.
 110.21
  
 PLEASE BE AWARE OF POSSIBLE COMMENTS
 FROM OTHER REVIEWER(S) WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  