2005-05-18 00:00:00*********** UNSAT ************
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM
 AND PANELS.
 PLEASE SEE RISER SHOWS A PANEL "L101",
 HOWEVER PANEL SCHEDULE SHOWS THIS? AS
 "LB101". THIS IS ALSO SHOWN AS 277/480V
 , HOWEVER THIS PANEL SEEMS TO BE ON THE
 LOAD SIDE OF A TRANSFORMER.
 PLEASE ALSO SEE PANEL "105" IS SHOWN AS
 120/208V WHICH IS SHOWN BEING FED FROM
 THE A 277/480V PANEL.
 PLEASE SEE PANEL "LB101"? ALSO SHOWS AN
 ADDITIONAL PANEL , YET THIS IS NOT ON
 RISER?
 PLEASE SEE NOTE AT PANEL ALSO INDICATES
 A PANEL "LB105"???
 PLEASE ALSO SEE PLANS AND PANELS SHOWN.
 PLEASE CORRELATE ALL OF THE ABOVE.
  
 2)NOTE: PLEASE PROVIDE ADDTIONAL
 INFORMATION ON LOAD OF EXISITNG SERVICE
 WITH ADDED LOADS PER NEC
 220.10,220.11,220.13 ETC ALL CONTINUOUS
 LOADS AT 125%215.3,230.42 ETC.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWERS WHICHMAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE BE SURE TO REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  