| Date |
Text |
| 2005-05-18 00:00:00 | *********** UNSAT ************ |
| | |
| | 1)NOTE: PLEASE CORRELATE RISER DIAGRAM |
| | AND PANELS. |
| | PLEASE SEE RISER SHOWS A PANEL "L101", |
| | HOWEVER PANEL SCHEDULE SHOWS THIS? AS |
| | "LB101". THIS IS ALSO SHOWN AS 277/480V |
| | , HOWEVER THIS PANEL SEEMS TO BE ON THE |
| | LOAD SIDE OF A TRANSFORMER. |
| | PLEASE ALSO SEE PANEL "105" IS SHOWN AS |
| | 120/208V WHICH IS SHOWN BEING FED FROM |
| | THE A 277/480V PANEL. |
| | PLEASE SEE PANEL "LB101"? ALSO SHOWS AN |
| | ADDITIONAL PANEL , YET THIS IS NOT ON |
| | RISER? |
| | PLEASE SEE NOTE AT PANEL ALSO INDICATES |
| | A PANEL "LB105"??? |
| | PLEASE ALSO SEE PLANS AND PANELS SHOWN. |
| | PLEASE CORRELATE ALL OF THE ABOVE. |
| | |
| | 2)NOTE: PLEASE PROVIDE ADDTIONAL |
| | INFORMATION ON LOAD OF EXISITNG SERVICE |
| | WITH ADDED LOADS PER NEC |
| | 220.10,220.11,220.13 ETC ALL CONTINUOUS |
| | LOADS AT 125%215.3,230.42 ETC. |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWERS WHICHMAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE BE SURE TO REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |