| 2005-08-22 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | A. FROM PREVIOUS REVIEW |
| | 3. SHT A-3 WATER HAMMER ARRESTORS SHALL |
| | BE LOCATED IN AN "EFFECTIVE RANGE" NOT |
| | IN THE CEILING AS SHOWN. PDI-WH 201 AND |
| | MANUF. INSTALLATION INSTRUCTIONS. |
| | 5. THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR PERMIT APPLICATION: |
| | D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2. - NO |
| | MANUF. SHEETS FOR WATER HEATER |
| | SUBMITTED. - MANUF. SHEET FOR BOILER |
| | INDICATE 1,046,000 BTU, BUT ISOMETRIC |
| | INDICATES 840,000 BTU. PLEASE CLARIFY. |
| | **************NEW COMMENTS************** |
| | 1B. SHT A-3 WATER RISER DIAGRAM SHOWS A |
| | 3/4" COLD WATER LINE TO THE AIR |
| | COMPRESSOR, BUT NO CONNECTION TO AIR |
| | COMPRESSOR IS SHOWN ON THE MANUF. |
| | SPECIFICATION SHEET. PLEASE CLARIFY WHAT |
| | THE WATER LINE TO THE COMPRESSOR IS FOR. |
| | IF CONNECTED TO THE COMPRESSOR, BACKFLOW |
| | PROTECTION IS REQUIRED. SECTION 104.2.1. |
| | 2B. SHT A-3 PIPE SIZING ON THE GAS RISER |
| | DIAGRAM IS NOT CORRECT PER TABLE 402(2). |
| | SEE RED LINE CORRECTIONS ON ONE SET OF |
| | PLANS. |
| | 3B. SEE COMMENT #1 OF THE ELECTRICAL |
| | PLAN REVIEW CONCERNING THE TITLE BLOCK |
| | OF THE ARCHITECT. |
| | |
| | REVIEW BY KEN STEVENS |