| 2005-06-16 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. SHTS A-2, A-3, A-4 ENGINEER SHALL |
| | LEGIBLY INDICATE THEIR NAME, ADDRESS AND |
| | LICENSE NUMBER ON EACH SHEET. NAME AND |
| | LICENSE NUMBER NOT SHOWN ON TITLE BLOCK. |
| | FAC 61G15-23.002(2) & FS 471.025. |
| | 2. SHT A-2 NOTES INDICATE FUTURE |
| | FIXTURES WITH SAFE WASTE TO FLOOR SINK. |
| | PLEASE CLARIFY. SAFE WASTE NOT APPROVED. |
| | INDICATE IF INDIRECT WASTE W/AIR GAP |
| | INTENDED. |
| | 3. SHT A-2 PLUMBING NOTES: AIR CHAMBERS |
| | ARE NOT APPROVED. DELETE NOTE. WATER |
| | HAMMER ARRESTORS REQUIRED AT QUICK |
| | CLOSING VALVES TO BE LOCATED NEAR THE |
| | FIXTURE IN AN "EFFECTIVE RANGE" NOT IN |
| | THE CEILING AS SHOWN. (REQD. AT W/M HOT |
| | & COLD). PDI-WH 201 & MANUF. |
| | INSTALLATION INSTRUCTIONS. |
| | 4. SHT A-2 WATER RISER DIAGRAM. WATER |
| | LINES TO THE HOSE BIBBS NOT SHOWN. |
| | SECTION 104.3.1.1. - SHOW ALL WATER |
| | PIPING ON RISER DIAGRAM. |
| | 5. THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR PERMIT APPLICATION: |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. NOT ALL LENGTHS SHOWN. |
| | SEE LINE FROM REGULATOR TO FIRST RISER. |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | C. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| | GAS CODE SECTION 304. |
| | D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | |