Plan Review Notes
Plan Review Notes For Permit 05050315
Permit Number 05050315
Review Stop P
Sequence Number 1
Notes
Date Text
2005-06-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS A-2, A-3, A-4 ENGINEER SHALL
 LEGIBLY INDICATE THEIR NAME, ADDRESS AND
 LICENSE NUMBER ON EACH SHEET. NAME AND
 LICENSE NUMBER NOT SHOWN ON TITLE BLOCK.
 FAC 61G15-23.002(2) & FS 471.025.
 2. SHT A-2 NOTES INDICATE FUTURE
 FIXTURES WITH SAFE WASTE TO FLOOR SINK.
 PLEASE CLARIFY. SAFE WASTE NOT APPROVED.
 INDICATE IF INDIRECT WASTE W/AIR GAP
 INTENDED.
 3. SHT A-2 PLUMBING NOTES: AIR CHAMBERS
 ARE NOT APPROVED. DELETE NOTE. WATER
 HAMMER ARRESTORS REQUIRED AT QUICK
 CLOSING VALVES TO BE LOCATED NEAR THE
 FIXTURE IN AN "EFFECTIVE RANGE" NOT IN
 THE CEILING AS SHOWN. (REQD. AT W/M HOT
 & COLD). PDI-WH 201 & MANUF.
 INSTALLATION INSTRUCTIONS.
 4. SHT A-2 WATER RISER DIAGRAM. WATER
 LINES TO THE HOSE BIBBS NOT SHOWN.
 SECTION 104.3.1.1. - SHOW ALL WATER
 PIPING ON RISER DIAGRAM.
 5. THE FOLLOWING INFORMATION IS REQUIRED
 FOR PERMIT APPLICATION:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. NOT ALL LENGTHS SHOWN.
 SEE LINE FROM REGULATOR TO FIRST RISER.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 C. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]