| 2005-06-02 00:00:00 | ****DENIED**** | | | | | | 1) PLEASE ILLUSTRATE THE FIRE RATING OF | | | THE BOILER ROOM DOOR IN HOURS. IE 1 1/2 | | | HRS OR 90 MINUTES ETC. | | | | | | 2) 2A-10B,C RATED FIRE EXTINGUISHERS ARE | | | REQUIRED TO BE MOUNTED AT A TRAVEL | | | DISTANCE NOT TO EXCEED 75'. | | | | | | 3) ALL CONSTRUCTION, ALTERATION AND | | | DEMOLITION TO COMPLY WITH NFPA 241. | | | | | | 4) SEPARATE SHOP DRAWINGS AND PERMITS | | | ARE REQUIRED FOR FIRE ALARM AND FIRE | | | SPRINKLER REMODELS IF APPLICABLE. | | | | | | | | | MIKE WENNERGREN, A/CAPTAIN | | | WPBFR(561) 835-2951 OR 805-6722 |
|