| Date |
Text |
| 2005-06-09 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | 1.) A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED, FS713.13. |
| | |
| | 2.)DECLARE AN OCCUPANCY FBC CHAPTER 4 |
| | AND CLARIFY SYSTEMS USED.PLEASE SEE |
| | CHAPTER 2, DEFINITIONS, DRY CLEANING |
| | SYSTEMS, FBC305,FBC407.17.IF THE |
| | BUSINESS PORTION IS A DIFFERENT |
| | OCCUPANCY THAN THE DRY CLEANING, SHOW |
| | REQUIRED SEPARATION FBC TABLE 704.1. |
| | EXITS ARE TO COMPLY WITH FBC1004. |
| | |
| | 3.)PLEASE EXPLAIN WHY THERE IS A 2 HR |
| | SEPARATION BETWEEN THE BOILER ROOM AND |
| | THE TENANT SPACE, BUT APPARENTLY ONLY A |
| | 1 HR BETWEEN THE BOILER ROOM AND THE |
| | ADJACENT TENANT. |
| | |
| | 4.)2-A1 DOES NOT SHOW A FIRE RATING |
| | FOR THE TENANT SEPARATION WALL.SEE |
| | FBC704.3 AND CLARIFY. |
| | |
| | 5.)FBC1012.1.4, THE REST ROOM DOOR |
| | BLOCKS THE PATH OF EGRESS. |
| | |
| | 6.)THE ENGINEER?S TITLE BLOCK IS TO BE |
| | IN COMPLIANCE WITH FAC61G15-23.002. |
| | |
| | |