2005-06-09 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.
  
 2.)DECLARE AN OCCUPANCY FBC CHAPTER 4
 AND CLARIFY SYSTEMS USED.PLEASE SEE
 CHAPTER 2, DEFINITIONS, DRY CLEANING
 SYSTEMS, FBC305,FBC407.17.IF THE
 BUSINESS PORTION IS A DIFFERENT
 OCCUPANCY THAN THE DRY CLEANING, SHOW
 REQUIRED SEPARATION FBC TABLE 704.1.
 EXITS ARE TO COMPLY WITH FBC1004.
  
 3.)PLEASE EXPLAIN WHY THERE IS A 2 HR
 SEPARATION BETWEEN THE BOILER ROOM AND
 THE TENANT SPACE, BUT APPARENTLY ONLY A
 1 HR BETWEEN THE BOILER ROOM AND THE
 ADJACENT TENANT.
  
 4.)2-A1 DOES NOT SHOW A FIRE RATING
 FOR THE TENANT SEPARATION WALL.SEE
 FBC704.3 AND CLARIFY.
  
 5.)FBC1012.1.4, THE REST ROOM DOOR
 BLOCKS THE PATH OF EGRESS.
  
 6.)THE ENGINEER?S TITLE BLOCK IS TO BE
 IN COMPLIANCE WITH FAC61G15-23.002.
  
  