Plan Review Notes
Plan Review Notes For Permit 05050240
Permit Number 05050240
Review Stop P
Sequence Number 1
Notes
Date Text
2005-05-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT P-1 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS. PLEASE
 CORRECT THE FOLLOWING:
 A. LOOP VENT DOWNSTREAM OF THE KITCHEN
 SINK DOES NOT SERVE ANY PURPOSE. PLEASE
 DELETE. SECTION 104.2.1
 B. THE KITCHEN SINK IS NOT VENTED AS
 SHOWN. RECOMMEND AN AIR ADMITTENCE VALVE
 FOR THE KITCHEN SINK OR AN ISLAND VENT.
 SECTIONS 901.2.1, 913, & 917.
 C. WASH MACHINE IS NOT VENTED PIPED AS
 SHOWN. SECTION 901.2.1. - CLEANOUT SHALL
 BE LOCATED 4FT ABOVE THE FLOOR. SECTION
 708.10.
 D. LAV IN POWDER ROOM IS NOT VENTED
 PIPED AS SHOWN. SECTION 901.2.1.
 E. SHOW ALL PIPE SIZES. SECTION
 104.2.1.
 F. SEE RED LINE CORRECTIONS ON ONE SET
 OF PLANS FOR REFERENCE.
 2. SHT P-1 WATER RISER DIAGRAM, WATER
 HAMMER ARRESTORS ARE REQUIRED AT THE
 WASH MACHINE, AND IF THERE IS A DISH
 WASHER AND/OR AN ICE MAKER IN THE REF.
 SECTION 604.9.
 3. THE PERSONAL SEAL, SIGNATURE AND DATE
 OF THE ARCHITECT SHALL APPEAR ON ALL
 ARCHITECTURAL DOCUMENTS TO BE FILED FOR
 PUBLIC RECORD. FAC 61G1-16.003 & FS
 481.2055.
  
 REVIEW BY KEN STEVENS