| 2005-05-26 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. SHT P-1 SANITARY RISER DIAGRAM DOES |
| | NOT MEET CODE REQUIREMENTS. PLEASE |
| | CORRECT THE FOLLOWING: |
| | A. LOOP VENT DOWNSTREAM OF THE KITCHEN |
| | SINK DOES NOT SERVE ANY PURPOSE. PLEASE |
| | DELETE. SECTION 104.2.1 |
| | B. THE KITCHEN SINK IS NOT VENTED AS |
| | SHOWN. RECOMMEND AN AIR ADMITTENCE VALVE |
| | FOR THE KITCHEN SINK OR AN ISLAND VENT. |
| | SECTIONS 901.2.1, 913, & 917. |
| | C. WASH MACHINE IS NOT VENTED PIPED AS |
| | SHOWN. SECTION 901.2.1. - CLEANOUT SHALL |
| | BE LOCATED 4FT ABOVE THE FLOOR. SECTION |
| | 708.10. |
| | D. LAV IN POWDER ROOM IS NOT VENTED |
| | PIPED AS SHOWN. SECTION 901.2.1. |
| | E. SHOW ALL PIPE SIZES. SECTION |
| | 104.2.1. |
| | F. SEE RED LINE CORRECTIONS ON ONE SET |
| | OF PLANS FOR REFERENCE. |
| | 2. SHT P-1 WATER RISER DIAGRAM, WATER |
| | HAMMER ARRESTORS ARE REQUIRED AT THE |
| | WASH MACHINE, AND IF THERE IS A DISH |
| | WASHER AND/OR AN ICE MAKER IN THE REF. |
| | SECTION 604.9. |
| | 3. THE PERSONAL SEAL, SIGNATURE AND DATE |
| | OF THE ARCHITECT SHALL APPEAR ON ALL |
| | ARCHITECTURAL DOCUMENTS TO BE FILED FOR |
| | PUBLIC RECORD. FAC 61G1-16.003 & FS |
| | 481.2055. |
| | |