Text |
| 2005-05-18 00:00:00 | *********** UNSAT ********** |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | AIC RATINGS FOR PANELS ARE SHOWN, |
| | HOWEVER PLEASE INDICATE FOR MAIN AND |
| | MTS. |
| | |
| | 2)NOTE: PLEASE SHOW SIZE OF GUTTER TO BE |
| | INSTALLED PER 366 OF THE NEC. |
| | PLEASE SEE PLANS SHALL NOT CONTAIN |
| | REFERENCE TO CODES IN WHOLE OR IN PART |
| | FBC 104.2.1 |
| | |
| | 3)NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| | ATTACHMENT PER 250.50. |
| | PLEASE ALSO SEE THE CODE SHALL NOT BE |
| | REFERENCED IN WHOLE OR IN PART. |
| | FBC 104.2.1 |
| | |
| | 4)NOTE: PLEASE SEE 250.6,250.24, NO |
| | EQUIPMENT GROUNDING CONDUCTORS SHALL BE |
| | INSTALLED FROM METER TI THE FIRST MEANS |
| | OF DISCONNECT. PLEASE SEE RISE INDICATES |
| | AND EQUIP. GRND. |
| | |
| | 5)NOTE: PLEASE SEE RISER INDICATES |
| | "GENERATORS CABLES" FOR PORTABLE GEN. |
| | UNIT. PLEASE CLARIFY THESE CABLES AS |
| | SHOWN. WILL THEY BE CONNECTED INTO ATS? |
| | WILL THEY TERMINATE INTO AN ENCLOSURE |
| | OUTSIDE? ETC. OR WILL THESE CABLES BE |
| | INSTALLED IN FUTURE? IF SO PLEASE ADD |
| | NOTE THAT CABLES BE FUTURE AND NOT |
| | INSTALLED AT THIS TIME. |
| | |
| | 6)NOTE: PLEASE SUBMIT MANUFACTURE SPECS |
| | FOR MTS. |
| | PLEASE SEE MTS SHALL HAVE A MANUAL MEANS |
| | OF DISCONNECT LOCATED ON THE OUTSIDE OF |
| | THE MTS. |
| | |
| | 7)NOTE: PLEASE VERIFY BOTH PANELS A AND |
| | B SEEM TO INDICATE MCB'S . THIS IS ONLY |
| | A NOTE. IFMLO, PLEASE ADJUST PANEL |
| | INFORMATION. |
| | |
| | 8)NOTE: PLEASE SEE NO LOAD CALCULATIONS |
| | WERE SUBMITTED. ONLY CONNNECTED LOADS |
| | SHOWN. |
| | PLEASE INCLUDE/SHOW ALL CONTINUOUS LOADS |
| | AND LARGEST MOTOR LOADS AT 125%. |
| | 215.3,230.42 ETC. |
| | |
| | 9)NOTE: PLEASE SEE 225.31-225.36 FOR |
| | FEEDERS FROM GEN. |
| | PLEASE SEE GROUPING OF MAINS REQUIRED. |
| | |
| | 10)NOTE: PLEASE VERIFY REQUIRED SIGN |
| | CIRCUIT PER 600.5 |
| | |
| | PLEASE SEE ANY OTHER COMMENTS FROM OTHER |
| | REVIEWER(S) WHICH MAY HAVE AN AFFECT ON |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE BE SURE TO REMOVE ALL OLD/VOIDED |
| | SHEETSAND ONLY INSERT NEW REVISED |
| | SHEETS INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | PLEASE SUBMIT ONE SET OF OLD/VOIDED |
| | SHEETS FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |