2005-05-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1. SHT A-7 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS. PLEASE
 CORRECT THE FOLLOWING:
 A. BATH #3 TUB IS NOT VENTED. SECTION
 901.2.1.
 B. LAUNDRY TRAY, FITTINGS SHALL
 DIRECTION WASTE IN DIRECTION OF FLOW.
 TEE FITTINGS ARE NOT APPROVED. SECTION
 706.3. (SEE RED LINE CORRECTION ON ONE
 SET OF PLANS.
 C. CLEANOUT AT WASH MACHINE SHALL BE
 LOCATED 4FT. ABOVE THE FLOOR. SECTION
 708.10.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692