| Plan Review Notes For Permit 05050207 |
| Permit Number |
05050207 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-06-03 00:00:00 | DENIED | | | | | | 1) FBC TABLE 600 DOES NOT ALLOW WALL | | | OPENINGS ON A ZERO LOT LINE. PLEASE | | | RELOCATE THE VENT SHOWN AT THE GARAGE ON | | | THE FLOOR PLAN ON A3. | | | | | | 2) THE ANCHOR SCHEDULE ON A6 SPECIFIES | | | USP THD210 HANGERS USING TAPCON | | | FASTENERS. THESE CONNECTORS ARE NOT | | | DESIGNED OR TESTED FOR USE WITH THESE | | | FASTENERS. PLEASE SPECIFY AN APPROPRIATE | | | MASONRY HANGER. | | | | | | 3) SUBMIT THE MANUFACTURER'S SPECS. AND | | | LISTING INFORMATION FOR THE ONE HOUR | | | FIRE RATED GLASS BLOCK. | | | | | | 4) SUBMIT THE EVAULATION REPORT FOR THE | | | ROBICO SHUTTERS. | | | | | | 5) THE PRODUCT APPROVAL SUBMITTED FOR | | | THE GLAZED FRENCH DOORS LIMITS THE GLASS | | | SIZE TO A MAXIMUM OF 14.869" WIDE AND | | | 55.619" IN HEIGHT. THE GLAZING IN THE | | | DOORS SHOWN ON THE ELEVATION HAVE LARGER | | | GLAZED AREAS. SUBMIT PRODUCT APPROVAL | | | FOR DOORS THAT WILL BE INSTALLED. | | | | | | 6) ADDITIONAL FEES ARE DUE FOR RADON AND | | | INCREASED CALCULATED VALUE. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|