Plan Review Notes
Plan Review Notes For Permit 05050207
Permit Number 05050207
Review Stop B
Sequence Number 1
Notes
Date Text
2005-06-03 00:00:00DENIED
  
 1) FBC TABLE 600 DOES NOT ALLOW WALL
 OPENINGS ON A ZERO LOT LINE. PLEASE
 RELOCATE THE VENT SHOWN AT THE GARAGE ON
 THE FLOOR PLAN ON A3.
  
 2) THE ANCHOR SCHEDULE ON A6 SPECIFIES
 USP THD210 HANGERS USING TAPCON
 FASTENERS. THESE CONNECTORS ARE NOT
 DESIGNED OR TESTED FOR USE WITH THESE
 FASTENERS. PLEASE SPECIFY AN APPROPRIATE
 MASONRY HANGER.
  
 3) SUBMIT THE MANUFACTURER'S SPECS. AND
 LISTING INFORMATION FOR THE ONE HOUR
 FIRE RATED GLASS BLOCK.
  
 4) SUBMIT THE EVAULATION REPORT FOR THE
 ROBICO SHUTTERS.
  
 5) THE PRODUCT APPROVAL SUBMITTED FOR
 THE GLAZED FRENCH DOORS LIMITS THE GLASS
 SIZE TO A MAXIMUM OF 14.869" WIDE AND
 55.619" IN HEIGHT. THE GLAZING IN THE
 DOORS SHOWN ON THE ELEVATION HAVE LARGER
 GLAZED AREAS. SUBMIT PRODUCT APPROVAL
 FOR DOORS THAT WILL BE INSTALLED.
  
 6) ADDITIONAL FEES ARE DUE FOR RADON AND
 INCREASED CALCULATED VALUE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  