Plan Review Notes
Plan Review Notes For Permit 05050204
Permit Number 05050204
Review Stop B
Sequence Number 2
Notes
Date Text
2005-08-10 00:00:00DENIED
  
 1) THE LOCATION OF THE STEEL HEADER
 SHOWN IN THE DETAIL ON THE 8-1/2 X 11
 SHEET IS NOT SPECIFIED ON THE PLANS.
  
 2) THE STEEL HEADER DETAIL ON THE 8-1/2
 X 11 SHEET DOES NOT HAVE THE REQUIRED
 MINIMUM INFORMATION. THE PROJECT IS NOT
 ADEQUATELY IDENTIFIED. THE FIRM LICENSE
 NUMBER IS REQUIRED. THE FIRM ADDRESS IS
 REQUIRED. THE PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENT IS REQUIRED. SEE
 FAC 61G-16.004.
  
 3) A SEPARATE PERMIT WILL BE REQUIRED
 FOR THE STORM PANELS UNLESS COMPLETE
 PRODUCT APPROVALS, INSTALLATION SCHEDULE
 AND KEY PLAN IS SUBMIITED AT TIME OF
 PERMIT.
  
 4)FBC 1005.4.5 (GLITCH AMENDMENTS
 JULY 1, 2003) REQUIRES AT LEAST ONE
 MEANS OF ESCAPE FROM A DWELLING WHEN
 SHUTTERED FOR IMPACT PROTECTION. THE
 MEANS OF ESCAPE SHALL BE WITHIN THE
 FIRST FLOOR OF THE DWELLING AND CAN NOT
 BE LOCATED IN A GARAGE. OCCUPANTS IN ANY
 PART OF THE DWELLING SHALL HAVE ACCESS
 TO IT WITHOUT HAVING TO PASS THROUGH A
 LOCKABLE DOOR NOT UNDER THEIR CONTROL.
 INDICATE HOW COMPLIANCE WILL BE
 ACHIEVED.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714