| 2005-06-02 00:00:00 | DENIED |
| | |
| | 1) THE 2650 CASEMENT WINDOW IN BEDROOM |
| | #2 IS REQUIRED TO COMPLY WITH EMERGENCY |
| | EGRESS CLEAR OPENING SIZE. SEE FBC |
| | 1005.4 |
| | |
| | 2) THE ANCHOR SCHEDULE ON A6 SPECIFIES |
| | USP THD210 HANGERS USING TAPCON |
| | FASTENERS. THESE CONNECTORS ARE NOT |
| | DESIGNED OR TESTED WITH THESE FASTENERS. |
| | PLEASE SPECIFY AN APPROPRIATE MASONRY |
| | HANGER. |
| | |
| | 3) THE CONDITIONED FLOOR AREA LISTED ON |
| | THE ENERGY CALC. FORMS DOES NOT MATCH |
| | THE A/C AREA SPECIFIED ON THE PLANS. |
| | PLEASE CORRECT. |
| | |
| | 4) THE GLASS BLOCK IN THE MASTER BATH |
| | ARE IN HAZARDOUS LOCATIONS AND AND ARE |
| | REQUIRED TO HAVE A MINIMUM UNIFORM FACE |
| | THICKNESS OF .25 INCH PER FBC 2405.2.2. |
| | |
| | 5) THE 9' HIGH FIXED GLASS WINDOWS IN |
| | THE LIVING ROOM EXCEED THE MAXIMUM |
| | HEIGHT SPECIFIED ON THE PRODUCT |
| | APPROVAL. |
| | |
| | 6) THE 12' WIDE TRANSOM WINDOW EXCEEDS |
| | THE MAXIMUM ALLOWED BY THE PRODUCT |
| | APPROVAL. |
| | |
| | 7) THE MULLION BETWEEN THE 12' SLIDING |
| | GLASS DOOR AND THE TRANSOM WINDOW |
| | EXCEEDS THE MAXIMUM DESIGN PRESSURE |
| | SPECIFIED IN THE PRODUCT APPROVAL. |
| | |
| | 8) SUBMIT STATE PRODUCT APPROVAL FOR THE |
| | 12' SLIDING GLASS DOOR. |
| | |
| | 9) SUBMIT THE EVALUATION REPORT FOR THE |
| | ROBICO SHUTTERS. |
| | |
| | 10) SUBMIT (2) COPIES OF A KEY PLAN AND |
| | INSTALLATION SCHEDULE FOR THE STORM |
| | PANELS. SPECIFY THE MOUNT TYPE AND |
| | FASTENER TYPE AND SPACING. |
| | |
| | 11) ADDITIONAL FEES ARE DUE FOR RADON |
| | AND INCREASED CALCULATED VALUE. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |