Plan Review Notes
Plan Review Notes For Permit 05050204
Permit Number 05050204
Review Stop B
Sequence Number 1
Notes
Date Text
2005-06-02 00:00:00DENIED
  
 1) THE 2650 CASEMENT WINDOW IN BEDROOM
 #2 IS REQUIRED TO COMPLY WITH EMERGENCY
 EGRESS CLEAR OPENING SIZE. SEE FBC
 1005.4
  
 2) THE ANCHOR SCHEDULE ON A6 SPECIFIES
 USP THD210 HANGERS USING TAPCON
 FASTENERS. THESE CONNECTORS ARE NOT
 DESIGNED OR TESTED WITH THESE FASTENERS.
 PLEASE SPECIFY AN APPROPRIATE MASONRY
 HANGER.
  
 3) THE CONDITIONED FLOOR AREA LISTED ON
 THE ENERGY CALC. FORMS DOES NOT MATCH
 THE A/C AREA SPECIFIED ON THE PLANS.
 PLEASE CORRECT.
  
 4) THE GLASS BLOCK IN THE MASTER BATH
 ARE IN HAZARDOUS LOCATIONS AND AND ARE
 REQUIRED TO HAVE A MINIMUM UNIFORM FACE
 THICKNESS OF .25 INCH PER FBC 2405.2.2.
  
 5) THE 9' HIGH FIXED GLASS WINDOWS IN
 THE LIVING ROOM EXCEED THE MAXIMUM
 HEIGHT SPECIFIED ON THE PRODUCT
 APPROVAL.
  
 6) THE 12' WIDE TRANSOM WINDOW EXCEEDS
 THE MAXIMUM ALLOWED BY THE PRODUCT
 APPROVAL.
  
 7) THE MULLION BETWEEN THE 12' SLIDING
 GLASS DOOR AND THE TRANSOM WINDOW
 EXCEEDS THE MAXIMUM DESIGN PRESSURE
 SPECIFIED IN THE PRODUCT APPROVAL.
  
 8) SUBMIT STATE PRODUCT APPROVAL FOR THE
 12' SLIDING GLASS DOOR.
  
 9) SUBMIT THE EVALUATION REPORT FOR THE
 ROBICO SHUTTERS.
  
 10) SUBMIT (2) COPIES OF A KEY PLAN AND
 INSTALLATION SCHEDULE FOR THE STORM
 PANELS. SPECIFY THE MOUNT TYPE AND
 FASTENER TYPE AND SPACING.
  
 11) ADDITIONAL FEES ARE DUE FOR RADON
 AND INCREASED CALCULATED VALUE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  