| Plan Review Notes For Permit 05050201 |
| Permit Number |
05050201 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-02-24 00:00:00 | | | | THESE COMMENTS WERE MADE ON 9/8/05 AND | | | HAVE NOT BEEN CORRECTED ON THE PLAN. IF | | | THESE ISSUES WERE CORRECTED IN THE FIELD | | | PLEASE CORRELATE THE DPAWINGS, IF NOT | | | CORRECTED IN THE FIELD, CORRECT SAME FOR | | | CODE COMPLIANCE. | | | | | | 1} KITCHEN COUNTERTOP RECEPTACLE PER | | | 210.52(C)(1), 210.8(A)(6). | | | | | | 2} POWDER ROOM RECEPTACLE PER 210.52(D), | | | 210.11(C)(3) AND 210.8(A)(1). | | | | | | 3} THE GROUNDING ELECTRODE CONDUCTOR | | | DOES NOT MEET THE MINIMUM SIZE REQUIRED | | | WHICH IS 1/0 CU PER 250.66. | | | | | | 4} MISSING RECEPTACLES FOR WALL SPACE | | | PER 210.52. SEE THE DEN AND BREAKFAST | | | ROOM ON REVIEWED PLAN FOR EXAMPLE. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | |
|