Plan Review Notes
Plan Review Notes For Permit 05050201
Permit Number 05050201
Review Stop E
Sequence Number 2
Notes
Date Text
2005-09-08 00:00:00REDLINEDTHE FOLLOWING MISSING.
  
  
 210.52C1 FOR MISSING GFI ALONG KITCHEN
 COUNTERSPACE.
 210.52D,210.11C3,210.8 FOR MISSING GFI
 IN PWDR RM.
 210.52 FOR MISSING RECETPS FOR WALL
 SPACE.
 250.66,310.15B6 FOR MIN GROUNDING
 ELECTRODE CONDUCTOR. MIN 1/0.
  
 THE ABOVE SHOULD BE REVISED WITH ANY
 OTHER REVISIONS BEFORE ROUGH ELECTRICAL
 INSPECTION.