Plan Review Notes
Plan Review Notes For Permit 05050201
Permit Number 05050201
Review Stop P
Sequence Number 1
Notes
Date Text
2005-05-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1. SHT A-7 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE, NOR DOES IT REFLECT THE
 FLOOR PLAN. PLEASE CORRECT THE
 FOLLOWING:
 A. THE GARAGE SINK SHALL NOT DRAIN
 THROUGH THE HORIZONTAL WET VENT OF THE
 BATHROOM FIXTURES. THIS SINK SHALL
 DISCHARGE DOWNSTREAM OF THE BATHROOM
 FIXTURES. SECTION 909.1
 B. THE CABANA BATH SHOWN ON THE FLOOR
 PLAN IS NOT SHOWN ON THE SANT. RISER
 DIAGRAM. SECTION 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]