| 2005-06-03 00:00:00 | DENIED |
| | |
| | 1) PLEASE INDICATE ON THE PLAN THAT THE |
| | GLASS BLOCK IN THE CABANA BATH IS ONE |
| | HOUR FIRE RATED. FBC TABLE 600 DOES NOT |
| | ALLOW OPENINGS ON THE ZERO LOT LINE. |
| | |
| | 2) THE ANCHOR SCHEDULE ON A6 SPECIFIES |
| | USP THD 210 HANGERS USING TAPCON |
| | FASTENERS. THESE CONNECTORS ARE NOT |
| | DESIGNED OR TESTED FOR USE WITH THESE |
| | FASTENERS. PLEASE SPECIFY AN APPROPRIATE |
| | MASONRY HANGERS. |
| | |
| | 3) SUBMIT MANUFACTURER'S SPECS. AND |
| | LISTING INFORMATION FOR THE ONE HOUR |
| | FIRE RATED GLASS BLOCK. |
| | |
| | 4) THE 12' STRUCTURAL MULLION BETWEEN |
| | THE SLIDING GLASS DOOR AND THE FIXED |
| | GLASS TRANSOM EXCEEDS THE MAXIMUM |
| | PRESSURE ALLOWED BY THE PRODUCT |
| | APPROVAL. |
| | |
| | 5) THE 12' WIDE FIXED GLASS TRANSOM |
| | ABOVE THE SGD EXCEEDS THE MAXIMUM WIDTH |
| | ALLOWED BY THE PRODUCT APPROVAL. |
| | |
| | 6) THE 9' WIDE FIXED GLASS WINDOW ABOVE |
| | THE (3) 25 SH WINDOWS IN THE DEN EXCEEDS |
| | THE MAXIMUM WIDTH ALLOWED BY THE PRODUCT |
| | APPROVAL. |
| | |
| | 7) SUBMIT THE EVALUATION/TEST REPORT FOR |
| | THE ROBICO STORM PANELS. |
| | |
| | 8) SUBMIT (2) COPIES OF A KEY PLAN AND |
| | INSTALLATION SCHEDULE FOR THE STORM |
| | PANELS. SPECIFY THE MOUNT TYPE, FASTENER |
| | TYPE AND FASTENER SPACING. |
| | |