| Date |
Text |
| 2005-06-15 00:00:00 | ************UNSAT *********** |
| | |
| | 1)NOTE: PLEASE SEE PERMIT APPLICATION |
| | DISCRIPTION MENTIONS AN ADDITON OF AN |
| | EXTERIOR SLAB? |
| | PLEASE UNDERSTAND THAT DUE TO THE |
| | DISCRIPTION, THIS PERMIT WAS OPENED AS A |
| | MISC PERMIT TYPE, WHEN INFACT THIS |
| | SHOULD HAVE BEEN OPENED AS A COMMERCIAL |
| | PERMIT. A FIRE REVIEW HAS SINCE BEEN |
| | ADDED AND PERMIT TYPE WILL NEED TO BE |
| | CHANGED. |
| | |
| | 2)NOTE: PLEASE SEE PLANS SUBMITTED DOES |
| | NOT MATCH APPLICATION FOR SCOPE PF WORK |
| | TO BE DONE. |
| | PLEASE SEE BLSG REVIEW COMMENTS FOR |
| | STOREFRONT AREA, PRODUCT APPROVALSETC. |
| | |
| | 3)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS FOR NEW EELCTRICAL AND CORRELATE |
| | WITH A PANEL SCHEDULE TO BE SUBMITTED. |
| | 215.5 |
| | PLEASE SEE 700.12E FOR CIRCUITING OF |
| | EM/EXT LTS. |
| | |
| | PLEASE BE SURE TO ANY COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY HAVE AN |
| | AFFECT ON ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |