Plan Review Notes
Plan Review Notes For Permit 05050168
Permit Number 05050168
Review Stop B
Sequence Number 1
Notes
Date Text
2005-06-03 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.
  
 2.)FBC11-4.1.6(1)(F) ACCESSIBLE
 BUILDINGS, ALTERATIONS, VERTICAL
 ACCESSIBILITY REQUIRED.
  
 3.)PROVIDE THE REMAINING 2ND FLOOR
 LAYOUT SO THAT CODE COMPLIANCE CAN BE
 DETERMINED.INCLUDE SQUARE FOOTAGE.
  
 4.)SHOW THE TWO MEANS OF EGRESS FROM
 THE 2ND FLOOR, NOTE 1, SHEET 1 OF 3.
 PROVIDE AN EXITING PLAN.IF THIS
 STAIRWAY IS A REQUIRED MEANS OF EGRESS,
 SHOW COMPLIANCE WITH FBC1006 AND
 FBC1007.
  
 5.)ALL DOCUMENTS PREPARED BY AND
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD
 ARE TO BE SIGNED, SEALED ORIGINALS,
 FAC61G15-23.002.A PHOTOCOPY WAS
 SUBMITTED.
  
 6.)FBC1007.2, STAIRS REQUIRED TO BE
 ACCESSIBLE SHALL COMPLY WITH FBC11-4.9.
  
 7.)FIRST FLOOR PLAN SHOWS THE STAIR
 WIDTH AS 3?3 OUTSIDE DIMENSION, SECOND
 FLOOR PLAN SHOWS AS INSIDE DIMENSION.
 CLEARLY SHOW STAIR WIDTH AND FRAMING
 DIMENSIONS, FBC1007.6.
  
 8.)FBC1007.5.5, EXTENSIONS REQUIRED AT
 THE TOP AND BOTTOM OF STAIRS ARE NOT
 SHOWN.ALSO SEE FBC11 FIGURE 19,
 FBC11-4.9.4.
  
 9.)SHOW MANEUVERING CLEARANCE FOR
 DOORS, FBC11 FIGURE 25.
  
 10.)A H/C BATH IS SHOWN; SHOW
 COMPLIANCE FBC11.
  