2005-06-08 00:00:00DENIED:
 1.PROVIDE DETAIL FOR THE CONDENSING
 UNIT RACK.
  
 2.INDICATE ELEVATION OF THE CONDESING
 UNIT.PER 2001 FBC(M)306.5, EQUIPMENT
 LOCATED AT A HEIGHT GREATER THAN 16 FT
 REQUIRE PERMANENT MEANS OF ACCESS.
  
 3.PROVIDE CLEARANCES BETWEEN THE
 CONDESING UNIT & THE EXTERIOR WALL.
 REFERENCE MANUFACTURER INSTALLATION
 INSTRUCTIONS FOR REQUIRED CLEARANCE.
 PLEASE NOTE, PER 2001 FBC(M)306.1,
 CLEARANCES AROUND EQUIPMENT INCLUDING
 OTHER INSTALLED EQUIPMENT (THE
 DISCONNECT).CLEARANCE SHALL BE
 SUFFICIENT TO ALLOW INSPECTION, SERVICE
 OR REPLACEMENT WITHOUT REMOVING ELEMENTS
 OF PERMANENT CONSTRUCTION.
  
 4.PLAN INDICATES FRESH AIR INTAKE 3 FT
 FROM THE CONDENSING UNIT IN WHICH THE
 FAN IS EXHAUSTING HEAT.THIS AIR SHOULD
 NOT BE RECIRCULATED PER 2001 FBC(M)
 501.3 & 401.5.1.PLEASE NOTE, THE
 OPENING LOCATION SHALL BE A MINIMUM OF
 10 FT FROM PARKING LOTS, STREETS OR
 ALLEYS.
  
 5.PROVIDE DETAIL FOR THE HANGING OF
 THE AHU.
  
 6.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001
 FBC(M)307.2.3.
  