| 2005-06-08 00:00:00 | DENIED: |
| | 1.PROVIDE DETAIL FOR THE CONDENSING |
| | UNIT RACK. |
| | |
| | 2.INDICATE ELEVATION OF THE CONDESING |
| | UNIT.PER 2001 FBC(M)306.5, EQUIPMENT |
| | LOCATED AT A HEIGHT GREATER THAN 16 FT |
| | REQUIRE PERMANENT MEANS OF ACCESS. |
| | |
| | 3.PROVIDE CLEARANCES BETWEEN THE |
| | CONDESING UNIT & THE EXTERIOR WALL. |
| | REFERENCE MANUFACTURER INSTALLATION |
| | INSTRUCTIONS FOR REQUIRED CLEARANCE. |
| | PLEASE NOTE, PER 2001 FBC(M)306.1, |
| | CLEARANCES AROUND EQUIPMENT INCLUDING |
| | OTHER INSTALLED EQUIPMENT (THE |
| | DISCONNECT).CLEARANCE SHALL BE |
| | SUFFICIENT TO ALLOW INSPECTION, SERVICE |
| | OR REPLACEMENT WITHOUT REMOVING ELEMENTS |
| | OF PERMANENT CONSTRUCTION. |
| | |
| | 4.PLAN INDICATES FRESH AIR INTAKE 3 FT |
| | FROM THE CONDENSING UNIT IN WHICH THE |
| | FAN IS EXHAUSTING HEAT.THIS AIR SHOULD |
| | NOT BE RECIRCULATED PER 2001 FBC(M) |
| | 501.3 & 401.5.1.PLEASE NOTE, THE |
| | OPENING LOCATION SHALL BE A MINIMUM OF |
| | 10 FT FROM PARKING LOTS, STREETS OR |
| | ALLEYS. |
| | |
| | 5.PROVIDE DETAIL FOR THE HANGING OF |
| | THE AHU. |
| | |
| | 6.AUXILIARY DRAIN PAN WITH OVERFLOW |
| | PROTECTION REQUIRED PER 2001 |
| | FBC(M)307.2.3. |
| | |