| 2005-05-18 00:00:00 | ********* PLANS REDLINED ********** | | | | | | 1)NOTE: PLEASE SEE OCP FOR 5KW HEAT IS | | | SHOWN AT 20A'S WITH A 24A CONNECTED | | | LOAD. PLEASE SEE 424.3B WHICH REQUIRED | | | OCP TO BE A MIN OF 125%. | | | THIS WAS REDLINED AND PLANS DO NOT NEED | | | TO BE REVISED, HOWEVER IF PLANS COME | | | BACK FOR ANY OTHER COMMENTS OR REVSIONS, | | | PLEASE CORRECT AT THAT TIME. | | | | | | *************************************** |
|