Plan Review Notes
Plan Review Notes For Permit 05050150
Permit Number 05050150
Review Stop E
Sequence Number 1
Notes
Date Text
2005-05-18 00:00:00********* PLANS REDLINED **********
  
 1)NOTE: PLEASE SEE OCP FOR 5KW HEAT IS
 SHOWN AT 20A'S WITH A 24A CONNECTED
 LOAD. PLEASE SEE 424.3B WHICH REQUIRED
 OCP TO BE A MIN OF 125%.
 THIS WAS REDLINED AND PLANS DO NOT NEED
 TO BE REVISED, HOWEVER IF PLANS COME
 BACK FOR ANY OTHER COMMENTS OR REVSIONS,
 PLEASE CORRECT AT THAT TIME.
  
 ***************************************