| Plan Review Notes For Permit 05050127 |
| Permit Number |
05050127 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-05-30 00:00:00 | DENIED: | | | PER 2001 FBC CHAPTER 13 SUB-CHAPTER 6, | | | TABLE 6-3 INDICATES PTAC UNITS WITH A | | | STANDARD RATING OF 8,000 BTU/HR SHALL | | | HAVE A MINIMUMEER OF 8.9.THE ENERGY | | | CALCULATIONS INDICATE THE UNIT RATING AS | | | ONLKY 8.5. | | | | | | PLEASE PROVIDE AN EQUIPMENT SCHEDULE | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|