Plan Review Notes
Plan Review Notes For Permit 05050127
Permit Number 05050127
Review Stop M
Sequence Number 1
Notes
Date Text
2005-05-30 00:00:00DENIED:
 PER 2001 FBC CHAPTER 13 SUB-CHAPTER 6,
 TABLE 6-3 INDICATES PTAC UNITS WITH A
 STANDARD RATING OF 8,000 BTU/HR SHALL
 HAVE A MINIMUMEER OF 8.9.THE ENERGY
 CALCULATIONS INDICATE THE UNIT RATING AS
 ONLKY 8.5.
  
 PLEASE PROVIDE AN EQUIPMENT SCHEDULE
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.