| Plan Review Notes For Permit 05050121 |
| Permit Number |
05050121 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-11-06 00:00:00 | PAUL SCHMITZ | | | FBC2001 FUEL GAS CODEPLAN REVIEW | | | FBC 2001 PLUMBING CODEPLAN REVIEW | | | FBC 2001 FL ACESSIBILITY CODE PLAN | | | REVIEW | | | DENIED | | | 1)SEC 104.2 DRAWINGS AND SPECIFICATIONS | | | PROVIDE A DWV ISOMETRIC DRAWING, SHOW | | | PIPE SIZES AND TYPE OF MATERIAL. | | | 2) MINIMUM PLUMBING FACILITIES | | | PROVIDE INFORMATION FOR DELETING | | | PLUMBING FIXTURES. | | | INCLUDE THE SEATING COUNT FOR THE GRAND | | | STAND WITH YOUR CALCULATIONS FOT MINIMUM | | | FIXTURES | | | ?P403.1 MINIMUM NUMBER OF FIXTURES. | | | PLUMBING FIXTURES SHALL BE PROVIDED | | | FOR THE TYPE OF OCCUPANCY AND IN THE | | | MINIMUM NUMBER SHOWN IN TABLE P403.1. | | | TYPES OF OCCUPANCIES NOT SHOWN IN TABLE | | | P403.1 SHALL BE CONSIDERED | | | INDIVIDUALLY BY THE CODE OFFICIAL.THE | | | NUMBER OF OCCUPANTS SHALL BE | | | DETERMINED BY THE BUILDING CODE. | | | OCCUPANCY CLASSIFICATION SHALL BE | | | DETERMINED IN ACCORDANCE WITH THE | | | FLORIDA BUILDING CODE, BUILDING. | | | END OF COMMENTS, QUESTIONS 561-805-6692 |
|