| 2005-05-25 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | |
| | A. SHT A-3 OF 6 SANITARY RISER DIAGRAM |
| | DOES NOT REFLECT THE FLOOR PLAN, NOR |
| | DOES IT MEET CODE REQUIREMENTS. THE |
| | FOLLOWING CORRECTIONS TO RISER WILL BE |
| | REQUIRED: |
| | 1. POWDER ROOM NOT SHOWN ON RISER. |
| | SECTION 104.2.1. |
| | 2. KITCHEN SINK NOT VENTED. SECTIONS |
| | 901.2.1 & 908.3 |
| | 3. WASH MACHINE SHALL BE SHOWN TO THE |
| | RIGHT AND DOWNSTREAM OF BATH ROOM. |
| | SECTION 104.2.1. |
| | 4. SHOWER MASTER BATH SHAL BE |
| | DOWNSTREAM OF THE WATER CLOSET. |
| | B. SHT A-1 OF 3 SANITARY RISER DIAGRAM |
| | DOES NOT REFLECT THE FLOOR PLAN, NOR |
| | DOES IT MEET CODE REQUIREMENTS. THE |
| | FOLLOWING CORRECTIONS TO RISER WILL BE |
| | REQUIRED. |
| | 1. RISER SHOWS SHOWERS, BUT FLOOR PLAN |
| | SHOWS TUBS. SECTION 104.2.1. |
| | 2. FIXTURES FROM 2ND FLOOR BATHROOM |
| | SHALL NOT DRAIN INTO THE VENT OF THE |
| | FIXTURES ON THE 1ST FLOOR. SECTION 908.3 |
| | 3. FIXTURE LAYOUT ON RISER DOES NOT |
| | REFLECT THE FIXTURE LAYOUT ON THE FLOOR |
| | PLAN. SECTION 104.2.1 |
| | C. SEE ATTACHED SHEET FOR EXAMPLES OF |
| | RISER DIAGRAMS THAT REFLECT THE FLOOR |
| | PLAN AND MEET CODE REQUIREMENTS. THIS IS |
| | INFORMATIONAL ONLY. |
| | |