Plan Review Notes
Plan Review Notes For Permit 05050117
Permit Number 05050117
Review Stop P
Sequence Number 1
Notes
Date Text
2005-05-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 A. SHT A-3 OF 6 SANITARY RISER DIAGRAM
 DOES NOT REFLECT THE FLOOR PLAN, NOR
 DOES IT MEET CODE REQUIREMENTS. THE
 FOLLOWING CORRECTIONS TO RISER WILL BE
 REQUIRED:
 1. POWDER ROOM NOT SHOWN ON RISER.
 SECTION 104.2.1.
 2. KITCHEN SINK NOT VENTED. SECTIONS
 901.2.1 & 908.3
 3. WASH MACHINE SHALL BE SHOWN TO THE
 RIGHT AND DOWNSTREAM OF BATH ROOM.
 SECTION 104.2.1.
 4. SHOWER MASTER BATH SHAL BE
 DOWNSTREAM OF THE WATER CLOSET.
 B. SHT A-1 OF 3 SANITARY RISER DIAGRAM
 DOES NOT REFLECT THE FLOOR PLAN, NOR
 DOES IT MEET CODE REQUIREMENTS. THE
 FOLLOWING CORRECTIONS TO RISER WILL BE
 REQUIRED.
 1. RISER SHOWS SHOWERS, BUT FLOOR PLAN
 SHOWS TUBS. SECTION 104.2.1.
 2. FIXTURES FROM 2ND FLOOR BATHROOM
 SHALL NOT DRAIN INTO THE VENT OF THE
 FIXTURES ON THE 1ST FLOOR. SECTION 908.3
 3. FIXTURE LAYOUT ON RISER DOES NOT
 REFLECT THE FIXTURE LAYOUT ON THE FLOOR
 PLAN. SECTION 104.2.1
 C. SEE ATTACHED SHEET FOR EXAMPLES OF
 RISER DIAGRAMS THAT REFLECT THE FLOOR
 PLAN AND MEET CODE REQUIREMENTS. THIS IS
 INFORMATIONAL ONLY.
  