| Plan Review Notes For Permit 05050117 |
| Permit Number |
05050117 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-05-17 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | | | | 1} THE APPLICATION CONTAINS THE WRONG | | | ADDRESS, OWNER INFORMATION AND PCN | | | NUMBER NOT FILLED IN. ALSO THE SQUARE | | | FOOTAGE WAS LEFT BLANK.PLEASE COMPLETE | | | PROPERLY. | | | | | | 2} THE DESIGNER OF RECORD MUST PRINT AND | | | SIGN NAME ON PLANS PER 104.2.1. FBC. | | | | | | 3} PLEASE PROVIDE A RISER DIAGRAM, LOAD | | | CALCULATIONS AND PANEL SCHEDULES. 215.5. | | | | | | 4} A SMOKE DETECTOR MUST BE ADDED AT THE | | | STAIR ON THE 1ST.FLOOR PER 905.2.2 FBC. | | | | | | 5} A RECEPTACLE MUST BE ADDED IN THE | | | LIVING ROOM PER 210.52. | | | | | | 6} THE FEED FOR THE SPA TUB MUST BE GFI | | | PROTECTED PER 680.43(A)(3). | | | | | | 7} INDICATE THE FOLLOWING REGARDING THE | | | GARAGE/ GUEST BUILDING. | | | A)THE PANEL LOCATION. | | | B) THE DISCONNECTING MEANS PER 225.31 & | | | 32. | | | C) GROUNDING PER 250.32. | | | D) THE BATH RECEPTACLE MUST BE GFI. 210 | | | 8(A)(1). | | | NOTE:THE GARAGE OR ART STUDIO ON THE | | | FIRST FLOOR MUST COMPLY WITH GFI | | | REQUIREMENT OF 208 OR SPACING | | | REQUIREMENTS OF 210.52. THE RECEPTACLES | | | ON THIS PLAN COMPLY WITH NEITHER. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|