Plan Review Notes
Plan Review Notes For Permit 05050117
Permit Number 05050117
Review Stop E
Sequence Number 1
Notes
Date Text
2005-05-17 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
  
 1} THE APPLICATION CONTAINS THE WRONG
 ADDRESS, OWNER INFORMATION AND PCN
 NUMBER NOT FILLED IN. ALSO THE SQUARE
 FOOTAGE WAS LEFT BLANK.PLEASE COMPLETE
 PROPERLY.
  
 2} THE DESIGNER OF RECORD MUST PRINT AND
 SIGN NAME ON PLANS PER 104.2.1. FBC.
  
 3} PLEASE PROVIDE A RISER DIAGRAM, LOAD
 CALCULATIONS AND PANEL SCHEDULES. 215.5.
  
 4} A SMOKE DETECTOR MUST BE ADDED AT THE
 STAIR ON THE 1ST.FLOOR PER 905.2.2 FBC.
  
 5} A RECEPTACLE MUST BE ADDED IN THE
 LIVING ROOM PER 210.52.
  
 6} THE FEED FOR THE SPA TUB MUST BE GFI
 PROTECTED PER 680.43(A)(3).
  
 7} INDICATE THE FOLLOWING REGARDING THE
 GARAGE/ GUEST BUILDING.
 A)THE PANEL LOCATION.
 B) THE DISCONNECTING MEANS PER 225.31 &
 32.
 C) GROUNDING PER 250.32.
 D) THE BATH RECEPTACLE MUST BE GFI. 210
 8(A)(1).
 NOTE:THE GARAGE OR ART STUDIO ON THE
 FIRST FLOOR MUST COMPLY WITH GFI
 REQUIREMENT OF 208 OR SPACING
 REQUIREMENTS OF 210.52. THE RECEPTACLES
 ON THIS PLAN COMPLY WITH NEITHER.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved