| Plan Review Notes For Permit 05050064 |
| Permit Number |
05050064 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-08-18 00:00:00 | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} LIGHTING FIXTURS ARE REQUIRED AS A | | | CONDITION OF CO. ONLY JUNCTION BOXES ARE | | | SHOWN ON THE PLAN IN THE FOYER AND AT | | | THE ENTRY. INDICATE BY SYMBOL, FIXTURES | | | THAT ARE REQUIRED BY ARTICLE | | | 210.70(A),(B),AND(C). | | | | | | 2} A DISPOSER HAS BEEN ADDED FOR THE | | | ISLAND SINK. IT DOES NOT APPEAR ON THE | | | PANEL SCHEDULE AND THEREFORE IN THE | | | CALCULATIONS. PLEASE LOCATE IN PROPER | | | PANEL AND CALCULATE PER 220.30, SINCE | | | THAT APPEARS TO BE THE CALCULATION | | | METHOD BEING USED. | | | | | | 3} A WINE COOLER AND ICE MACHINE/MAKER | | | HAVE BEEN ADDED TO THE PLAN BUT NOT THE | | | SCHEDULE, SEE NOTE #2. | | | | | | 4} BATH #3 RECEPTACLE AT THE VANITY DOES | | | NOT MEET THE 3' SPACING REQUIREMENT OF | | | 210.52(D). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | | | | |
|