| 2005-06-14 00:00:00 | DENIED |
| | |
| | 1.IMPACT PROTECTION REQUIRED FBC 1606 |
| | |
| | 2.SHOW HOW SEPERATION BETWEEN EXISTING |
| | BUILDING AND NEW GUEST COTTAGE WILL |
| | COMPLY WITH FBC TABLE 600.SHOW SIZES |
| | OF OPENINGS IN EXISTING BUILDING |
| | ADJACENT TO NEW BUILDING. |
| | |
| | 3.SUBMIT PRODUCT APPROVALS FOR |
| | EXTERIOR DOORS. |
| | |
| | 4.ALL PRODUCT APPROVALS WITH QUALITY |
| | ASSURANCE (MIAMI-DADE) FOR EXAMPLE |
| | REQUIRE THE FOLLOWING STATE APPROVALS TO |
| | BE ATTACHED. |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | NOTE: ROOF OVERHANGS APPEAR TO OVERLAP. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |