| Date |
Text |
| 2005-05-25 00:00:00 | DENIED |
| | |
| | 1) SUBMIT A COPY OF THE PAID RECEIPT FOR |
| | THE COUNTY IMPACT FEES. |
| | |
| | 2) THE 2650 CASEMENT WINDOW IN BEDROOM |
| | #2 IS REQUIRED TO COMPLY WITH EMERGENCY |
| | EGRESS CLEAR OPENING SIZE. SEE FBC |
| | 1005.4 |
| | |
| | 3) THE ANCHOR SCHEDULE ON A6 SPECIFIES |
| | USP THD210 HANGERS USING TAPCON |
| | FASTENERS. THESE CONNECTORS ARE NOT |
| | DESIGNED OR TESTED WITH THESE FASTENERS. |
| | PLEASE SPECIFY AN APPROPRIATE MASONRY |
| | HANGER. |
| | |
| | 3) THE PRODUCT APPROVAL SUBMITTED FOR |
| | THE GLAZED FIBERGLASS DOOR IS LIMITED TO |
| | A HEIGHT OF 6'8". THE PLANS SPECIFY |
| | DOORS 8' IN HEIGHT. SUBMIT CORRECT |
| | PRODUCT APPROVAL. |
| | |
| | 4) THE NOA SUBMITTED FOR THE SERIES 640 |
| | CASEMENT WINDOWS WITH FL# 2766 DOES NOT |
| | HAVE THE CORRECT NOA NUMBER. SUBMIT THE |
| | NOA WITH THE NUMBER LISTED ON THE FL |
| | PRODUCT APPROVAL. |
| | |
| | 5) SUBMIT THE MANUFACTURER'S SPECS. AND |
| | LISTING INFORMATION FOR THE ONE HOUR |
| | FIRE RATED GLASS BLOCK. |
| | |
| | 6) SUBMIT THE FL PRODUCT APPROVAL AND |
| | INSTALLATION DRAWINGS FOR THE 6'X 8' |
| | OVER HEAD GARAGE DOOR. |
| | |
| | 7) SUBMIT THE SBCCI EVALUATION REPORT |
| | FOR THE STORM PANELS. |
| | |
| | 8) SUBMIT (2) COPIES OF A KEY PLAN AND |
| | AN INSTALLATION SCHEDULE FOR THE STORM |
| | PANELS. INDICATE THE MOUNT TYPE, |
| | FASTENERS, FASTENER SPACING, ETC. |
| | |
| | 9) ADDITIONAL FEES ARE DUE FOR RADON AND |
| | INCREASE IN CALCULATED VALUE OF THE |
| | STRUCTURE. |
| | |
| | 10) CONTRACTOR NEEDS TO UPDATE INSURANCE |
| | INFORMATION WITH THE CITY. |
| | |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |