Plan Review Notes
Plan Review Notes For Permit 05042221
Permit Number 05042221
Review Stop B
Sequence Number 1
Notes
Date Text
2005-05-25 00:00:00DENIED
  
 1) SUBMIT A COPY OF THE PAID RECEIPT FOR
 THE COUNTY IMPACT FEES.
  
 2) THE 2650 CASEMENT WINDOW IN BEDROOM
 #2 IS REQUIRED TO COMPLY WITH EMERGENCY
 EGRESS CLEAR OPENING SIZE. SEE FBC
 1005.4
  
 3) THE ANCHOR SCHEDULE ON A6 SPECIFIES
 USP THD210 HANGERS USING TAPCON
 FASTENERS. THESE CONNECTORS ARE NOT
 DESIGNED OR TESTED WITH THESE FASTENERS.
 PLEASE SPECIFY AN APPROPRIATE MASONRY
 HANGER.
  
 3) THE PRODUCT APPROVAL SUBMITTED FOR
 THE GLAZED FIBERGLASS DOOR IS LIMITED TO
 A HEIGHT OF 6'8". THE PLANS SPECIFY
 DOORS 8' IN HEIGHT. SUBMIT CORRECT
 PRODUCT APPROVAL.
  
 4) THE NOA SUBMITTED FOR THE SERIES 640
 CASEMENT WINDOWS WITH FL# 2766 DOES NOT
 HAVE THE CORRECT NOA NUMBER. SUBMIT THE
 NOA WITH THE NUMBER LISTED ON THE FL
 PRODUCT APPROVAL.
  
 5) SUBMIT THE MANUFACTURER'S SPECS. AND
 LISTING INFORMATION FOR THE ONE HOUR
 FIRE RATED GLASS BLOCK.
  
 6) SUBMIT THE FL PRODUCT APPROVAL AND
 INSTALLATION DRAWINGS FOR THE 6'X 8'
 OVER HEAD GARAGE DOOR.
  
 7) SUBMIT THE SBCCI EVALUATION REPORT
 FOR THE STORM PANELS.
  
 8) SUBMIT (2) COPIES OF A KEY PLAN AND
 AN INSTALLATION SCHEDULE FOR THE STORM
 PANELS. INDICATE THE MOUNT TYPE,
 FASTENERS, FASTENER SPACING, ETC.
  
 9) ADDITIONAL FEES ARE DUE FOR RADON AND
 INCREASE IN CALCULATED VALUE OF THE
 STRUCTURE.
  
 10) CONTRACTOR NEEDS TO UPDATE INSURANCE
 INFORMATION WITH THE CITY.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714