| Notes |
| Date |
Text |
| 2005-08-04 00:00:00 | ******DENIED****** | | | | | | 1) PLEASE SEE BUILDING REVIEW COMMENT IN | | | REGARDS TO MINIMUM HEADROOM REQUIREMENT | | | FOR STAIRS. NOT LESS THAN 80". NFPA 101, | | | SECTION 7.1.5.3. | | | | | | 2) PLEASE SHOW LOCATION OF NEW OR | | | EXISTING SMOKE DETECTORS. | | | | | | 3) AS INDICATED ON LAST REVIEW, IF WORK | | | IMPACTS FIRE SPRINKLER SYSTEM OR ANY | | | OTHER LIFE SAFETY EQUIPMENT, SEPARATE | | | SHOP DRAWINGS AND PERMITS WILL BE | | | REQUIRED FOR REMODEL. | | | | | | | | | MIKE WENNERGREN, CAPTAIN | | | WPBFR(561) 804-4756 | | | PLAN REVIEW(561) 805-6722 |
|