| Plan Review Notes For Permit 05042220 |
| Permit Number |
05042220 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-06-04 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1. MORE INFORMATION IS REQUIRED ON THE | | | WATER WALL. PLEASE INDICATE THE METHOD | | | FOR SUPPLYING THE WATER TO THE SYSTEM. | | | SECTION 104.2.1. IF A SUPPLY LINE IS | | | CONNECTED TO THE POTABLE WATER, SOME | | | METHOD OF BACKFLOW PREVENTION IS | | | REQUIRED. | | | SHT P-1 INDICATES NO DRAIN REQUIRED FOR | | | THE WATER FEATURE, BUT DETAIL ON SHT A-3 | | | INDICATES AND 1-1/4" OVERFLOW DRAIN. | | | PLEASE CLAIRFY. WHERE WOULD THE 1-1/4" | | | OVERFLOW DRAIN CONNECT TO THE SANT. | | | SYSTEM. SECTION 104.2.1. | | | 2. APPLICATION STATES "DESCRIBE PROJECT | | | IN DETAIL" BUT NO MENTION OF THE WATER | | | WALL, MOVING OF THE POWDER ROOM FIXTURES | | | OR BUILDING THE SOFFIT IS INDICATED. | | | PLEASE CLARIFY. | | | 3. SEPARATE PERMIT REQUIRED FOR | | | PLUMBING. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|